Set Common Output for HOLD & ABORT
It is possible to set any of the outputs for use as a common output indication, to show activation of
HOLD and ABORT functions for both Single and Dual flood zone Panels. A Sounder or Relay output
can be used to provide this common indication.
NOTE:
For dual flood zone panels, it is an EN 12094-1 requirement that a common output is used to
indicate HOLD and ABORT activation from either flood zone area.
To set a common output for HOLD and ABORT functions:
•
Turn
Activate Controls
key clockwise to
On
, or use the keypad to enter Authorised User
(Access level 2) code 1111:
o
Press
✓
key
o
Use Up/Down arrow keys to increase/decrease the number value
o
Use Left/Right arrow keys to move to the next digit in the 4-digit sequence
o
When all 4 digits have been set to the code 1111, press the
✓
key again
•
The Main Menu will become available for operation
•
On the
Main Menu
, use Left/Right arrow keys to move cursor to
CONFIG
menu icon
•
Press
✓
key to select
CONFIG
menu. The digital display will show the following message:
Enter Level 3 Access Code
•
Use the keypad to enter code 3333:
o
Press
✓
key
o
Use the Up/Down arrow keys to increase/decrease the number value
o
Use the Left/Right arrow keys to move to the next digit in the 4-digit sequence
o
When all 4 digits have been set to the code 3333 press
✓
key once again. The Access
level 3 menu will become available for operation.
•
On the
CONFIG
Menu, use Left/Right arrow keys to move the cursor to highlight
Devices
option and then press
✓
key to gain access to it.
•
On the
CONFIG Devices
sub-menu, use left/right arrow keys to select either
SOUNDER
or
RELAY Menu
, depending on which type of output is to be used for common HOLD or ABORT
indication:
o
SOUNDER: With the cursor over the
SOUNDER Menu
press
✓
button.
o
Use Left/Right arrow keys to toggle between the various Sounders
o
Use Up/Down arrow keys to select either:
▪
option 12 for
ABORT
or
▪
option 13 for
HOLD
.
o
RELAY: With the cursor over the
RELAY Menu
press
✓
button.
o
Use Left/Right arrow keys to toggle between the various Relays
o
Use Up/Down arrow keys to select either:
▪
option 6 for
ABORT
or
▪
option 7 for
HOLD
.
•
Once required output and option have been selected, press
✓
button to change displayed
setting from
NO
(de-selected) to
YES
(selected for activation). Further presses of
✓
button will
toggle between these two states.
www.acornfiresecurity.com