ESPRIT Gas Extinguishing User Manual
CONFIGURING THE PANEL
54
Approved Document Ref: UI-ESG-01 Issue 2.0
CONFIG Menu: PANEL
Under the
PANEL
sub-menu, the following sub-menus are available to configure the panel controls
and outputs:
•
LEARN
•
OPTIONS
•
SET DEFAULT PARAMETERS
•
SET PASSWORDS
CONFIG PANEL Menu: LEARN
To set the system to learn what internal cards, external devices and RSUs are connected, access the
LEARN PANEL
sub-menu:
•
On the
CONFIG Menu
, highlight
PANEL
option and then press
✓
key to gain access to it.
•
Next highlight the
LEARN
option, under the
CONFIG PANEL
menu, and press
✓
key to
select it.
•
The system will perform a learning routine, in order to acknowledge the Internal Cards
installed, the External Devices connected to it, and the P-BUS (Peripheral BUS, which is
achieved using a RS485 network) connection. The following information will be displayed
in turn, each accompanied by a progress bar:
o
LEARNING INTERNAL CARDS:
o
LEARNING EXTINGUISHANT:
o
LEARNING P-BUS:
•
On completion of the learning routine, the
LEARN PANEL
sub-menu will display all the
options that were found available:
o
INTERNAL CARDS
: The
LEARN PANEL
menu will display the internal cards
found connected, or not, indicated by
YES
or
NO
:
-INTERNAL CARDS-
1: PSU Card: YES/NO
2: Gas Card ONE: YES/NO
3: Gas Card TWO: YES/NO
4: AREA TWO FASCIA: YES/NO
5: Relay ONE: YES/NO
6: Relay TWO: YES/NO
o
Press return
key to accept.
o
EXTINGUISHANT OUTPUT
: The
LEARN PANEL
menu will display the
extinguishant release options:
- EXTINGUISHANT OUTPUT-
1: AREA 1: SOLENOID/ONE METRON/TWO METRON/THREE METRON/NOT
PRESENT
2: AREA 2: SOLENOID/ONE METRON/TWO METRON/THREE METRON/NOT
PRESENT
o
Use the Up/Down arrow keys to move between extinguishant area.
o
Press the
✓
key to change between
values
–
Solenoid/One Metron/Two
Metron/Three Metron/Not Present
.