ESPRIT Gas Extinguishing User Manual
CONFIGURING THE PANEL
55
Approved Document Ref: UI-ESG-01 Issue 2.0
o
Press return
key again
o
P-BUS
: The
LEARN PANEL
sub-menu will display a list containing all 16 RSUs
and show if they are connected or not, using the P-BUS, indicated by the Gas
area the RSU is connected to, or
NOT PRESENT
:
-P-BUS-
1: FIRST RSU: GAS AREA ONE/GAS AREA TWO/NOT PRESENT
2: SECOND RSU: GAS AREA ONE/GAS AREA TWO/NOT PRESENT
3: THIRD RSU: GAS AREA ONE/GAS AREA TWO/NOT PRESENT
to
14: FOURTEENTH RSU: GAS AREA ONE/GAS AREA TWO/NOT PRESENT
15: FIFTEENTH RSU: GAS AREA ONE/GAS AREA TWO/NOT PRESENT
16: SIXTEENTH: GAS AREA ONE/GAS AREA TWO/NOT PRESENT
o
For each of the RSUs fitted, configure to show which Gas Area they are installed in:
▪
Use the Up/Down arrow keys to select each RSU to be configured
▪
Press the enter
✓
key to toggle through the options,
GAS AREA ONE/GAS
AREA TWO/NOT PRESENT
,
•
Press the return
key to finally accept. A short acknowledgement sound will be
present.
Note:
The status of the RSUs may be changed, using the Up/Down arrow keys and the
✓
key
to change between
GAS AREA ONE, GAS AREA TWO
or
NOT PRESENT
. However, any
differences between detected devices and changes made by user, will result in a System Fault
condition. The
General Fault
and
System Fault
status LEDs will be illuminated pulsing, with
an accompanying fault tone from the internal buzzer. Additionally, on return to the Title screen,
a
FAULT
display will list the applicable faults. This condition will require the panel to be re-
configured to clear.
CONFIG PANEL Menu: OPTIONS
To configure the panel sounder options, access the
OPTIONS
menu:
•
On the
CONFIG
Menu
, highlight
PANEL
option and then press
✓
key to gain access to it.
•
Next highlight the
OPTIONS
icon, under the
CONFIG PANEL
menu and press
✓
key to select
it.
•
The information available under
PANEL OPTIONS
menu will be presented as follows (use the
up/down arrows key to navigate between following settings):
1: ZONES RESOUND 2ND ALARM: YES/NO
2: Sounder ONE FARE: YES/NO
3: Sounder TWO FFRE: YES/NO
4: RESET INHIBIT TIME (Min): nnnn
•
Use the Up/Down arrow keys to move between options 1 to 4
•
For options 1 to 3, press enter
✓
key to toggle between
YES
or
NO
,
as required.
•
For option 4, press enter
✓
key to enable changes, then use Up/Down arrow keys to set
the time the sounders activation is to be inhibited by (up to a maximum of 30 minutes).
Press the
✓
key to exit
RESET INHIBIT TIME
adjustment function.
Note:
If
SOUNDER ONE FARE
and/or
SOUNDER TWO FFRE
are set to
YES
, their status
(
NORMAL
/
ACTIVE
) will be displayed on the LCD screen title display, and in place of the event
counts (
A nn F nn D nn O nn
) on any of the
EVENT
reports (
ALARM
,
FAULT
,
DISABLE
and
OTHER
).