ESPRIT Gas Extinguishing User Manual
CONFIGURING THE PANEL
56
Approved Document Ref: UI-ESG-01 Issue 2.0
Note:
When a circuit goes into Fire Alarm, option 4 sets a time delay of up to 30 minutes before
the sounders and extinguishant release are activated. This is to protect against possible false
alarms. This option is overridden if a second circuit goes into Alarm, or the extinguishant is
released manually.
•
Press return
key to exit Menu. A short sequence of buzzer beeps will indicate the changes
have been stored in memory.
•
Further presses of return
key will bring back to Title screen.
CONFIG PANEL Menu: DEFAULT
To return the panel to its factory default setting, access the
DEFAULT
menu.
•
On the CONFIG Menu, highlight
PANEL
option and then press
✓
key to gain access to it.
•
Next highlight the
DEFAULT
icon, under the
CONFIG PANEL
menu and press
✓
key to select
it.
•
The following information will be displayed on the digital monitor:
ARE YOU SURE?
Set Panel Defaults?
•
Use the Left/Right arrows key to choose between
YES
or
NO
options and then press the
✓
key in order to enable your action.
•
If
NO
value has been selected, then the system will return to
CONFIG PANEL
Menu and all
the current settings will be maintained.
•
If
YES
is selected, then all current settings will be overwritten, and the system will return to
original factory settings. A short acknowledgement sound will be present.
Caution is recommended before choosing the YES value for the DEFAULT option!
Choosing this option will remove ALL configuration that has been set and will return the
panel to its factory default settings.
•
Next press the return
key once to return to
CONFIG PANEL
Menu.
A short
acknowledgement sound will be present.
CONFIG PANEL Menu: PASSWORD
To set the 4-digit access codes, access the
Password
menu:
•
On the
CONFIG Menu
, highlight
PANEL
option and then press
✓
key to gain access to it.
•
Highlight the
Password
option under the
CONFIG PANEL
menu and press
✓
key
again.
•
The
Set Password Menu
will be presented as follows:
OLD User Password: 1111
Back
User Password: 0000
Confirm
•
Use the Up/Down arrow keys to increase/decrease the number value
•
Use the Left/Right arrow keys to move to the next digit in the 4-digit sequence
•
When all 4 digits have been set to the required new code press
✓
key once again.
•
Press the return
key once to return to
Panel
menu.
YES
S
NO
www.acornfiresecurity.com