CONFIGURING THE PANEL
57
Approved Document Ref: UI-ESG-01 Issue 2.0
CONFIG Menu: GAS CARD
To configure the Gas Card:
•
On the
CONFIG Menu
, highlight
PANEL
option and then press
✓
key to gain access to it.
•
Highlight
GAS CARD
option and then press
✓
key in order to gain access to it.
•
The Gas Card information will be displayed as follows:
CONFIG GAS Card GAS AREA ONE/TWO
1: EXTINGUISH DELAY (Secs) : nnnn
2: EXTINGUISH DUR (Secs) : nnnn
3: EXTRACT Time (Min) : nnnn
4: FLOODING Time (Secs) : nnnn
5: EXTRACT OUTPUT: AUTO/MANUAL/NO EXTRACT
6: FLOW SWITCH PRESENT: NO/YES
7: PRESSURE SWITCH: NORMAL OPEN/CLOSED
8: MANUAL RELEASE MODE: DELAYED/IMMEDIATE
-CONTRIBUTORY ALARM-
9: Zone ONE: YES/NO
10: Zone TWO: YES/NO
11: Zone THREE: YES/NO
12: Zone FOUR: YES/NO
13: Zone FIVE: YES/NO
14: Zone SIX: YES/NO
15: CONTRIBUTORY COUNT: ONE/TWO/THREE/FOUR
•
Configure the various options for the Gas Card(s), as follows:
o
Use Left/Right arrow keys to toggle between Gas Areas
ONE
and
TWO
o
Use Up/Down arrow keys to select required option
o
For options 1 to 4, press
✓
key to activate time change function
o
Use Up/Down arrow keys to adjust indicated time (n) to required time (within limits
available)
o
Press
✓
key to de-activate time change function
o
Up/Down arrow keys now return to selecting required option
o
For options 5 to 15, press
✓
key to toggle between the indicated states.
Note:
for single Flood Zone Panels, access to options 12 to14 (zones 4 to 6) in this menu
will be blocked
•
When selections are completed press return
key to return to Title screen. A short
sequence of buzzer beeps will indicate changes have been stored in memory.