ESPRIT Gas Extinguishing User Manual
CONFIGURING THE PANEL
59
Approved Document Ref: UI-ESG-01 Issue 2.0
•
The information available under
SOUNDERS
menu will be presented as follows:
SOUNDERS
<PSU SNDR ONE/PSU SNDR TWO/GAS AREA ONE STAGE
1/GAS AREA ONE STAGE 2/GAS AREA TWO STAGE 1/GAS AREA TWO STAGE
2>
-PRE-ACTIVATED Stage-
1: Sounder: CONTINUOUS / PULSING / OFF
-ACTIVATED Stage-
2: Sounder: CONTINUOUS / PULSING / OFF
-RELEASED Stage-
3: Sounder: CONTINUOUS / PULSING / OFF
-EXTRACT Stage-
4: Sounder: CONTINUOUS / PULSING / OFF
-NON-CONTRIB ALARM-
5: Sounder: CONTINUOUS / PULSING / OFF
-OTHER OUTPUTS-
6: IN ALARM: CONTINUOUS / PULSING / OFF
7: IN ALERT: CONTINUOUS / PULSING / OFF
8: IN CLASS CHANGE: CONTINUOUS / PULSING / OFF
9: IN EVAC: CONTINUOUS / PULSING / OFF
10: IN DELAY: CONTINUOUS / PULSING / OFF
11: Sounder CAN BE SILENCED: YES / NO
12: Sounder ABORT OUTPUT: YES / NO
13: Sounder HOLD OUTPUT: YES / NO
Note:
Single Flood Zone Panels will have 4 Sounders (2 Common PSU Card Sounders and 2
Sounders for the Gas Card). Dual Flood Zone Panels will have 6 Sounders (2 Common PSU
Card Sounders and 2 Sounders for each Gas Card fitted).
•
Use Left/Right arrow keys to toggle between the various Sounders (
PSU SNDR ONE
,
PSU
SNDR TWO
,
GAS AREA ONE STAGE 1
,
GAS AREA ONE STAGE 2
, etc.)
•
Use Up/Down arrow keys to select required Sounder Output option.
•
Once option selected, press the
✓
key to change indicated state.
Note:
For options 1 to 10, each press of
✓
key will toggle between the 3 available states
(
CONTINUOUS
,
PULSING
and
OFF
).
Note:
For options 11 to 13, each press of
✓
key will toggle between
YES
and
NO
.
•
When the required state for each of the options has been set, press the return
key to
return to
CONFIG Devices
sub-menu. A short sequence of buzzer beeps will indicate the
changes have been stored in memory.
•
Further presses of return
key will exit back to Title screen.
www.acornfiresecurity.com
www.acornfiresecurity.com