HAGAB – INSTALLATION, OPERATION AND MAINTENANCE

INTACT

Fire/Fire gas damper

HAGAB – INSTALLATION, OPERATION AND MAINTENANCE

INTACT

Fire/Fire gas damper

According to EN1366-2 

Circular damper for prevention of the spread of fire and fire 
gas. For installation against or separated from fire-rated struc-
tural elements. The damper has a fire resistance rating of  
EI 60 (ve i 

 o)S, EI 60 (ho i 

 o)S. See EC certificate 

0402-CPR-SC1119-11. Tested according to a harmonised  
product standard, which means that the product is CE marked.  
RISE certification provides increased safety and quality.

TABLE OF CONTENTS

1. INSTALLATION OF DAMPERS  

AGAINST STRUCTURAL ELEMENTS 

 

2

2. INSTALLATION OF DAMPERS  

WITH AN INSTALLATION SLEEVE 

 

4

3. INSTALLATION OF DAMPERS
SEPARATED 

WALLS 

   6

4. INSTALLATION OF DAMPERS 
AGAINST 

JOISTS 

   8

5. INSTALLATION OF DAMPERS 
AGAINST JOISTS (ONLY FOR

 Ø

400-630) 9 

OPERATION AND MAINTENANCE 

           10

Accessories
-Angle bracket (supplied)
-Installation sleeve
-Protection grilles

The installations of the dampers are tested 
according to SS-EN 1366-2:2015.

The walls can be flexible walls or equivalent, 
that fulfills fire resistance class EI60. 

Solid building components, rigid walls or 
floors, can be of cellular concrete block,  
concrete, solid brick or equivalent, that  
fulfills fire resistance class EI60. 

≥75

≥200

≥200

≥75

[mm]

The minimum distance between dampers must be 200 mm.
The minimum distance to the floor/wall must be 75 mm.

Drawing name:

Summary of Contents for INTACT

Page 1: ...OF DAMPERS AGAINST STRUCTURAL ELEMENTS 2 2 INSTALLATION OF DAMPERS WITH AN INSTALLATION SLEEVE 4 3 INSTALLATION OF DAMPERS SEPARATED WALLS 6 4 INSTALLATION OF DAMPERS AGAINST JOISTS 8 5 INSTALLATION...

Page 2: ...and the wall with a fire resistant sealant 2 Angle brackets Fix the supplied angle brackets spaced evenly around the damper Angle bracket supplied 3 Fix the duct Fix the duct to be installed through...

Page 3: ...to the duct system e g when installing as a closing device or transfer air device the damper must be fitted with protection grilles on the non connected side The minimum permissible distance between t...

Page 4: ...in the hole Place the damper casing flush against the structural element centre it in the hole and fix laterally with the damper and duct system suspension devices 3 Fix the duct Fix the duct to be i...

Page 5: ...nimum permissible distance between the damper blade in the open position and the grille is 50 mm Install the thermal sensor Check that the screws and the thermal sensor do not hinder damper blade move...

Page 6: ...t the wall structural element and screw them together 2 Install the duct Centre the duct against the installation sleeve The space between the installation sleeve and connecting duct can be fitted wit...

Page 7: ...according to the insulation supplier s instructions Note that the insulation must cover the whole damper 6 No connection in the duct system If the damper is not connected to the duct system e g when i...

Page 8: ...x the duct to be installed through the structural element against the damper fitting with plate screws Check that the screws do not hinder damper blade movement Note the installation direction of the...

Page 9: ...fitting with flat head screws Check that the screws do not hinder damper blade movement Note the installation direction of the damper 4 Sealing Seal between the damper and the joists with a fire resi...

Page 10: ...year INTERNAL CONTROL VIA INSPECTION COVER OR CLEANING HATCH IN CONNECTING DUCT Check by triggering the smoke detector so the damper closes Check that the damper blade closes and opens freely by switc...

Reviews: