HAGAB – INSTALLATION, OPERATION AND MAINTENANCE

INTACT

Fire/Fire gas damper

5. INSTALLATION OF DAMPERS 
AGAINST JOISTS

 

WITHOUT CAULKING AND REFINISHING

Approved for outside fire cell sizes Ø400 - 630 mm.

1. 

Hole dimensions 

 

Damper dim 10 mm.

2. Angle brackets

 

Fix the supplied angle brackets spaced evenly around the 
damper.

Angle bracket

 (supplied)

3. Fix the duct.

 

Fix the duct to be installed through the structural element 
against the damper fitting with flat head screws. Check that 
the screws do not hinder damper blade movement. 

Note the installation direction of the damper.

4. Sealing

 

Seal between the damper and the joists with a fire-resistant 
sealant.

5. Seal around the edge

 

Place the damper casing flush against the structural element, 
centre it in the hole and fix with the angle brackets. Seal 
around the edge of the damper with a fire-resistant sealant.

6. Fix the duct and install the thermal sensor. 

Fix the duct to the damper fitting with screws and install the 
thermal sensor.  

Check that the screws and the thermal sensor do not hinder 
damper blade movement.

Drawing name:

Summary of Contents for INTACT

Page 1: ...OF DAMPERS AGAINST STRUCTURAL ELEMENTS 2 2 INSTALLATION OF DAMPERS WITH AN INSTALLATION SLEEVE 4 3 INSTALLATION OF DAMPERS SEPARATED WALLS 6 4 INSTALLATION OF DAMPERS AGAINST JOISTS 8 5 INSTALLATION...

Page 2: ...and the wall with a fire resistant sealant 2 Angle brackets Fix the supplied angle brackets spaced evenly around the damper Angle bracket supplied 3 Fix the duct Fix the duct to be installed through...

Page 3: ...to the duct system e g when installing as a closing device or transfer air device the damper must be fitted with protection grilles on the non connected side The minimum permissible distance between t...

Page 4: ...in the hole Place the damper casing flush against the structural element centre it in the hole and fix laterally with the damper and duct system suspension devices 3 Fix the duct Fix the duct to be i...

Page 5: ...nimum permissible distance between the damper blade in the open position and the grille is 50 mm Install the thermal sensor Check that the screws and the thermal sensor do not hinder damper blade move...

Page 6: ...t the wall structural element and screw them together 2 Install the duct Centre the duct against the installation sleeve The space between the installation sleeve and connecting duct can be fitted wit...

Page 7: ...according to the insulation supplier s instructions Note that the insulation must cover the whole damper 6 No connection in the duct system If the damper is not connected to the duct system e g when i...

Page 8: ...x the duct to be installed through the structural element against the damper fitting with plate screws Check that the screws do not hinder damper blade movement Note the installation direction of the...

Page 9: ...fitting with flat head screws Check that the screws do not hinder damper blade movement Note the installation direction of the damper 4 Sealing Seal between the damper and the joists with a fire resi...

Page 10: ...year INTERNAL CONTROL VIA INSPECTION COVER OR CLEANING HATCH IN CONNECTING DUCT Check by triggering the smoke detector so the damper closes Check that the damper blade closes and opens freely by switc...

Reviews: