background image

1

6E 7518.f

6E 7518.f

§

Programmable light 
sensitive switch

User instructions

EE110, 04011

Operating principle

The EE110, 04011 programmable light sensi-
tive  switch controls light sytems according to
a program set by the user, depending on
natural illumination;

- during the work authorization period,

depending on wheter the measured light
level is below or above the order, it will be
switched on or off.

- during the work banning period, the

contact remains without tension, whatever
the light level is.

The light sensitive switch includes a built
in time delay which avoid unnecessary
switching due to temporary factors such
as car beams etc...

Description

The programmable light sensitive switch EE110,
04011 has two main functions:

• a light sensitive switch comprising:

Œ

Override selector switch to allow permanent
setting ON or OFF , auto or test mode.



Lighting range selector

Ž

Potentiometer to set light level



Indicator to show output switching.

• a programmer to establish the automatic operating
cycle.

Permanent overrides

the override selector 

Œ

allows permanent

overrides which have priority on programming
and the measured light level.

permanent override “ON"

permanent override "OFF"

Setting of the working level

the “test” position of the override selector 

Œ

makes easier the setting of the working level,
it removes the ON and OFF delay.

Select the sensitivity range which suits whith
the application (selector 



) :

5 to 100 lux (low light level) applica-
tion examples : public lighting, shop
windows, signals....

50 to 2000 lux (high light level) appli-
cation examples : control of shades.

At the appropriate moment of the day, put the
selector 

Œ

in “test” position; turn the poten-

tiometer 

Ž

up to the switching point (the

indicator 



lights); put the selector back to

position “auto”, the normal operating mode of
the device.

auto

test

auto

test

Lux

T

6:00

8:00

17:00

23:00

ON

ON

OFF

OFF

OFF

19

18

20

Programming

OFF

ON

Switching dial 

Work 
banning 
period

Work 
authorization 
period

Time setting

 

 

Œ

Ž





L
N

5

18

19 20

6

9

10

Mounting of the cell

To ensure a good working of the light sensitive
switch, the cell must not be influenced by
artificial light or direct solar radiation and has
to be sheltered from dust and humidity.

In case of disconnection of the link between
the cell and the light sensitive switch, the
output of the device will be switched on.

Make sure the light sensitive switch is unplug-
ged before connecting the cell.

Technical specification

Electrical specification:

- voltage rating : 230V ~+10/-15% 50 Hz
- consumption : 1,5 VA max.
- output : 1 voltage free changeover contact

Max. breaking capacity :  
AC1  

16A 250V~

incandescent lamp  

2000W 230V~

halogen lamp   

1000W 230V~

fluorescent lamp :
uncompensated 1000W 

230V~

compensated in series (10μF) 1000W 230V~
// compensated (15μF) 

200W 230V~

duo :

1000W 230V~

Functional characteristics:

- 2 sensitivity ranges 5 to 100 lux,

50 to 2000 lux

- daily cycle 
- program setting : 15 minutes increments
- accuracy : ± 6 min./ annum
- operating reserve : at 20°C, 200 h after

beeing connected for 120 h

- ON and OFF delay :  15 to 60 s.
- working temperature :  

-30 °C to +60 °C (cell),
-10 °C to +50 °C (modular device)

- storage temperature : 

- 20 °C to +60 °C

- protection class (cell) : IP54
- insulation class (cell) :  II

Connection capacity: 

- modular device: 0,5 to 4 mm

2

- cell : 0,75 to 2,5 mm

2

- Max. lenght between cell and modular

device : 50 m

- mounting of the cell with 2 screws Ø 2,5 mm.

A warranty period of 24 months is offered on hager products,
from date of manufacture, relating to any material of manufac-
turing defect. If any product is found to be defective it must be
returned via the installer and supplier (wholesaler). 
The warranty is withdrawn if :
- after inspection by hager quality control dept the device is
found to have been installed in a manner which is contrary to
IEE wiring regulations and accepted practice within the indus-
try at the time of installation.
- the procedure for the return of goods has not been followed.
Explanation of defect must be included when returning goods.

Warranty

GB

Reviews: