6T7379B
2
Media center
domovea customer
www.domovea.com
Router / Switch
LAN
PoE
Spécifi cations techniques / Technische Daten / Technical characteristics
Alimentation KNX
Versorgungsspannung KNX
KNX Supply voltage
KNX bus 30V DC
Très basse tension de sécurité externe
Externe Sicherheits kleinspannung
External SELV power supply
24V DC (TBTS, SELV, ZLVS )
Consommation sur la ligne bus
Stromaufnahme aus der Buslinie
Power usage from the bus line
10 mA max - 30V DC
Consommation sur l’alimenta tion
auxiliaire
Stromaufnahme aus der Hilfsspannung-
versorgung
Power usage from the auxiliary power
supply
150 mA max - 24VDC
Communication réseau Ethernet
Ethernet Netzwerkkom munikation
Ethernet Network com munication
100 BaseT (100 Mbit/s)
PoE interdit/ verboten/ prohibited
Raccordement bus
Busanschlüsse
Bus line connection
0,6 - 0,8 mm²
Prise d’alimentation
Spannungs versorgung anschluss
Auxiliary power connection
0,75 - 2,5 mm ²
Prise réseau Ethernet / IP
Ethernet / IP Netzwerk anschluss
Ethernet / IP network
RJ 45
T° de fonctionnement
Betriebstemperatur
Operating temperature
0 °C —> + 45 °C
T° de stockage
Lagertemperatur
Storage temperature
- 20 °C —> + 70 °C
Indice de protection
Schutzart
Degree of protection
IP 20
Encombrement
Abmessungen (1TE= 18 mm)
Dimensions
6 x 17,5 mm
Z
TJA450 is an interface of bus KNX with your local
home Ethernet network.
Software
TJA450 is equipped with server software domovea.
It operates in link with IP clients equipped with OS
systems Windows XP, Windows Vista, Windows 7
or Windows Media Center.
Installation
1. Connect 24V DC power supply.
2. Connect Bus KNX 30V DC.
3. Connect the Ethernet cable (Local Network).
Installation with DHCP Server
Set Switch 1 to “on-line” position. TJA450 is
expecting the IP address of the DHCP Server.
Green LED 2 fl ickers during this stand-by period.
Once the IP address is received, green LED 2 stays
on fi xed lighting.
Installation without DHCP Server
Set Switch 1 to “on-line” or “off-line” position.
Green LED 2 fl ickers for 40 seconds, then TJA450
switches automatically to IP 192.168.0.253 (default
IP address).
Installation in the distribution box
TJA450 should be preferably installed in the VDI
box of your installation. If the installation does not
include a VDI box, make sure that high/low currents
are separated.
Z
Caution
!
- This device must be installed only by a qualified
electrician.
- Not for outdoor use.
- PoE prohibited.
State LED
Description
Failure correction
2
3
4
Off
Disconnected network cable
Connect the network cable
Fixed Red
Confl ict of IP address
Check IP addresses used on the
server
Green fl ickering
Standby waiting for DHCP Server IP
address
/
Fixed Green
Address IP Received
/
2
3
4
Off
Disconnected network cable
Connect the network cable
Fixed Red
Portal unavailable or connection denied
Check your Internet connection
Green fl ickering
Connecting to desired portal
/
Fixed Green
Connection to desired portal successful /
2
3
4
Red fl ickering
Power supply problem
Check power supply
Fixed Red
Defective product
Contact Hager Support Department
Green fl ickering
Domovea Server starting
/
Fixed Green
Domovea Server running
/