Product Presentation

The EGN200AU and EGN400AU time switches are 

clocks with weekly and annual electronic programming 

that automatically control different loads. 

Examples of applications: street lighting, neon signs, 

shop windows, monuments, facades etc. 

The integrated astronomical clock can be set to 

switch loads according to sunset and sunrise times.

The connection of an EEN002 / EEN003 twilight 

sensor (optional) makes it possible to switch the loads 

according to brightness. 

Programming by mobile terminal is recommended 

via Bluetooth

®

 technology by using the configuration 

application (iOS and Android) available as a free 

download.

Main features

•  Product delivered with updated time and day.

•  Programming by application via Bluetooth

®

 or local 

programming (except annual).

•  Backlit screen.

•  Automatic daylight savings time change.

•  Astronomical mode.

•  Programming by day or group of days.

•  200 or 400 program steps (depending on version) 

On, Off, pulses  .

•  Permanent overrides On or Off.

•  Temporary overrides On or Off.

•  Exceptions (temporary, permanent or delayed) can 

be activated remotely using a push button.

•  Bar graph display of the daily profile for 2 or 4 

channels (depending on version).

•  Programmable when off via screen only (with limited 

functionality).

•  Twilight switch function via an EEN002 or EEN003 

wired brightness sensor. 

Display and keys

Screensaver

Date

Bluetooth

®

 

enabled

Time
Channel 

status

A, B, 

C, D 

(depending 

on version)

Press once to turn backlight on, 

twice to display the home screen.

Home screen

0

6

12

18

24

Bar graph 

of the daily 

profile

Brightness

Time

Display the 

manual 

controls 

screen

(brief press)

Change 

the channel

A, B, C or D

(depending on 

the version)

Selection of days 

(cursor)

LMMJVSD

Channel 

currently 

displayed

Figure 1:

 Presentation of the screensaver and home 

screen

Functional features

•  Programming capacity: 200 or 400 steps depending 

on the model

•  Min. time between 2 steps: 1 minute

•  Precision of operation: ± 0.25 s / day

•  The product switches to the standby state (display 

off) after 1 minute of no voltage or inactivity. 

It returns to auto mode when power is restored or 

when a key is pressed.

• Bluetooth

®

 radio frequency: 2.4 - 2.483 GHz 

  - Max. transmitting power: 10 mW

  - Range: 10 m in free field 

  - Version: 4.2 

•  Mobile/PC terminal configuration

  - iOS version equal to or greater than 8

  - Android version equal to or greater than 5.1

  - Windows version equal to or greater than 10

  - Bluetooth

®

: version equal to or greater than 4.2 

•  Insulation class: 2

•  Action type: 2B

•  Software class: Class A

•  Ball test T°: 75 °C

•  Upstream protection: 16 A circuit breaker

•  Stated voltage and current for EMC emissions 

testing: 230 V~ / - 0.5 A

•  Protection class: IP20 (case), IP30 (case under 

faceplate) 

•  Impact resistance: IK04

Battery

•  Power reserve: 10 years with no action

•  Non-replaceable and non-rechargeable

Case

•  EGN200AU dimensions: 36 mm / 2 modules

•  EGN400AU dimensions: 72 mm / 4 modules

•  DIN rail mounted independent product according to 

EN 60715

Environment

•  Operating T° -5 °C to +45 °C

•  Storage T° -25 °C to +70 °C

•  Relative humidity: 95 % to 20°C

•  Pollution category 2

Connection with screw terminals

•  Rigid 0.2 to 4 mm

2

•  Flexible 0.2 to 2.5 mm

2

•  Screw recess: PH1

Initial set-up

With the configuration application 

If the application is used to configure the clock, install 

as described below.

1.

 Directly access the download link of the application 

by scanning the 

QR code

 printed on the clock and 

the instructions with a mobile terminal.

2.

 Download and install the configuration application.

3.

 Check that Bluetooth

®

 is enabled (see

Settings / 

BLUETOOTH

 chapter).

4.

  Pair your mobile terminal and your clock via the 

Bluetooth

®

 application.

5.

 Program your product via the application. To do this, 

follow the application instructions to configure the 

clock.

With the local programming interface

During initial set-up, set the following:

• language;

•  year, month, day;

•  hour and minutes;

•  daylight savings time change.

Press keys 

3

/

4

 to enter the required settings on the 

display.

Press the 

ok

 key to confirm.

Once the settings are completed, the clock switches 

to automatic mode.

Manual commands

From the screen saver, press one of the 4 keys twice 

to activate the backlight and then switch to the 

home screen. Display the manual controls screen by 

pressing the 

ok

 key.

From the screen saver, press one of the 4 keys twice 

to activate the backlight and then switch to the 

home screen. Display the manual controls screen by 

pressing the 

ok

 key.

HOME 

SCREEN

MANUAL

CONTROLS

HOME

SCREEN

Press a key 

twice

All programming and settings are based on the 

following principle:

• Keys 

3

/

4

 are used to navigate between outputs A, 

B, C and D (depending on version).

•  briefly press the OK key repeatedly to display the 

various manual control options for the selected 

output.

Connection diagram

•  Device to be installed only by a qualified 

electrician according to the standards 

applicable in the country.

•  Before connecting the brightness sensor, or 

before carrying out any operations on 

it, cut the 230 V power supply to the clock.

1

  Override input 

or exception

2

   Brightness 

sensor

Figure 2:

  EGN200AU connection diagram (2 outputs)

1

  Override input or exception

2

  Brightness sensor

Image 3:

 EGN400AU connection diagram (4 outputs)

Technical specifications

Electrical specifications

•  Supply voltage: 230 V~ +10/-15% 

and 240 V~ ± 6% 

•  Network frequency: 50/60 Hz 

•  Consumption: EGN200AU < 350 mW / EGN400AU 

< 500 mW

•  Output 2 or 4 non-insulated changeover contacts 

(depending on the version) 

•  Max. breaking capacity: AC1 μ 16A 230 V~ 

•  Incandescent light bulbs, power relay with contact: 

normally open / 2300 W_normally closed / 1500 W

•  Halogen lamps: 230 V~ 2300 W 

•  Fluorescent tubes, compensated // (max. 45 μF), 

power relay with contact: normally open / 400 W_

normally closed / 300 W

•  Fluorescent tubes, uncompensated, series 

compensated: 1000 W 

•  Compact fluorescent lamps and LED lamps, power 

relay with contact: normally open / 400 W_normally 

closed / 300 W

•  Min. breaking capacity: AC1 100 mA 230 V~ 

•  Rated shock voltage: 4 kV 

•  Maximum switching speed at full load: 6 switching 

cycles/minute

6LE005569B

1

EGN200AU, EGN400AU

Hager Mood

z

Multi-function Time Switch

2 Channel Bluetooth

®

Multi-function Time Switch

4 Channel Bluetooth

®

Additional information 

is available by 

scanning the displayed 

QR code with your 

mobile terminal.

  Complies with

 IMDA Standards

DA101847

Reviews: