For your safety
Technical changes reserved
5
-
Take into account the power loss of the installed devices and wiring in
comparison with the specified power loss of the distribution board
(DIN EN 61439-1: 2012-06 (VDE 0660-600-1: 2012-06),
DIN EN 61439-2: 2012-06 (VDE 0660-600-2: 2012-06).
-
The housing must be aligned at its final installation site. To do this, lift the
housing at the corners and adjust the height using shim plates.
-
After doing so, the housing should be in a horizontal position.
-
Secure the housing to prevent it from tilting (installation material provided).
-
Make sure that the fire protection sealing strips are not damaged.
-
Check the door locks properly when closing the housing.