53
Operation
Programming
Parameter Characteristics :
Menu (Setup)
Setup
LCD
Denomination
Definition
Setting range
Default value
Type of network*
Number of active conductors
of controlled network
(refer to annexes)
1BL, 2BL, 2NBL, 3NBL,
4NBL, 41 NBL
4NBL
Network nominal
voltage
Phase-Neutral voltage
for 1BL & 41NBL
Phase-Phase voltage for others
from 110 V to 480 V
400 VAC
Network nominal
frequency
Network nominal frequency
50Hz ou 60Hz
50 Hz
Source 1 -
Switch Ior II
configuration
Source 1 (controlled and
displayed) linked to switch I or II
(depending on cabling)
I, II
I
Normally opened
or closed
Normally opened or closed
NO ou NC
NO
1 2
Network priority
selection
Keypad selection (1 or 2)
1 ou 2
1
Manual Retransfer
Activation of the feature
Yes ou No
No
Type of control
logic selection
Impulse or contactor
Imp, Con
Imp
Number of
permutation
counter Reset
Allows source 1 -> source 2
automatic sequences counter
reset
Yes ou No
No
Programming code
modification
Possible to change the
programming code
from 0001 to 9999
1000
* refer to annexes.