HTG410H
Devices installation and settings
7.1.2.4.4 Setting the stop bit
Press button
to access this configuration item.
Example: Stop = 2
7.1.2.6 Function test for the electrical wiring connections
During testing, device SM102E must be supplied with current and
voltage to all connections. Testing requires a power factor of the
installation between 0.6 and 1. If the power factor of the installation
falls outside this range, the test cannot be performed. In the case of
4 BL / 3 BL / 2 BL / 1 BL only the connection of the current transformer
is tested. In the case of 4 NBL and 3 NBL the connection as a whole is
controlled.
Error
Error description
Err0
There is no error
Err 1 / 2 / 3
Reversed polarity of current transformer on phase 1 / phase 2 / phase 3
Err4
Reversed polarity of voltage between V1 and V2
Err5
Reversed polarity of voltage between V2 and V3
Err6
Reversed polarity of voltage between V3 and V1
7.1.2.5 To quit and save programming
confirm