background image

Designation

H

W

D

JKD2884PM

1850mm

465mm

165.5mm

Fixing Centres

A

B

C

D

JKD2884PM

365mm

100mm

1200mm

600mm

Warranty

This distribution board is offered with a 24 month warranty against 
defective material or manufacture. If a warranty claim is necessary, 
please call the technical support number given at the bottom of the page 
and we will be pleased to help.

Interface Characteristics

Rated & operational voltage (Un / Ue)

415V a.c. 50Hz

Rated insulation voltage (Ui)

690V a.c. 50Hz

Rated impulse withstand voltage (Uimp)

4kV

Rated current of the Assembly (In

A

)

JKD2xxxPM 125A

Rated current of an Outgoing circuit (In

C

)

MCB 0.5A - 63A (marked rated current on device)
RCBO 6A - 40A (marked rated current on device)

Rated Current of Pan Assembly

Upper Pan In = 125A (RDF = 1)

Middle Pan In = 125A (RDF = 1)
Lower Pan In = 125A (RDF = 1)

Rated conditional short-circuit current of the ASSEMBLY (Icc) 

10kA

1

 with equipment and arrangements specified in Hager’s technical 

documentation / catalogue.

MCB/RCBO 10kA rating applied as BS EN 61439-3 is intended for use 

by ordinary persons.

1

Current limitation characteristics specified in Hager’s technical 

documentation / catalogue

Protection against electric shock

DBO shall be installed in an electrical system conforming to IEC 60364 / 

BS 7671

Rated diversity factor (RDF) / Values of assumed loading

10 way - 24 way = 0.5

Note:  RDF only applies to continuously and simultaneously loaded 

circuits. 

Rated frequency (

f

n)

50 Hz

Pollution degree

2

Types of system earthing for which the ASSEMBLY is designed

TNC-S, TN-S and TT when installed in an electrical system conforming 

to BS 7671

Intended locations

Indoor use only

Stationary ASSEMBLY
Degree of protection

IP3XD with Door Closed

IP2XC with Door Open and compliment of outgoing devices and or 

blanks fitted.

Intended use

Distribution boards intended to be operated by ordinary persons (DBO)

Electromagnetic compatibility (EMC) classification

EMC Environment B

External design 

Wall-mounted, surface type, enclosed assembly.

Mechanical impact protection

IK05

The type of construction

Fixed parts

DBO Type

Type B DBO

Accessories

JK01B

Single Pole Blank

JK222PK

JK1 / JK2 Door Lock Kit

JK2PLATEM

Gland Plate + Drill Markings

JK107DL

7 Input Data Logger with TCP/IP

Hager Technical Help Line: 01952 675 689

Hager Technical Fax: 01952 675 557

Website: www.hager.co.uk