The luminosity detector RF this document refers to is a Quicklink
RF product. It can be recognised by its
cfg
configuration push
button. Quicklink
indicates the configuration without tools mode.
These products can also be configured to E mode by the TX100 or in S mode by ETS via the media coupler .
This document describes the configuration principle with the ETS software via the media coupler and the functions available in
this mode.
Within the same installation, a single configuration mode may be used.
To reuse a product that has already been programmed in another installation by TX100 or quicklink
, with ETS, it is
necessary to perform a factory reset for the product.
The luminosity detector is a battery-powered KNX radio transmitter. It is designed for the automatic control of shutters or blinds
(see Figure 1). According to the measured luminosity and the thresholds set on the product, it controls the raising or lowering of
the shutters and blinds to provide sun protection and/or a dusk function. Luminosity is measured sensor attached to the window
with a suction cup. The product does not transmit luminosity values.
1: Lux < threshold
= Shutter up
2: Lux > threshold
= Shutter descends to the level of the sensor then rises for 1 s to ensure detection again
2: Lux > threshold
= Shutter up
4: Lux < threshold
= Shutter fully lowered
5: Lux < threshold
= No automatic raising
The KNX Up or Down controls are completely dependent:
•
On the choice of the function selected on the potentiometers: sun protection (Threshold > 1500 lux) and/or dusk function
(threshold < 500 lux),
•
On the configuration of the luminosity threshold(s).
These choices and settings are only accessible on the product (no parameters in ETS).
A button on the front of the product allows the user to interrupt automatic operation (no more radio transmissions except for the
Status indication - Battery status
object). The effect of this button can be inhibited by configuration, leading to permanent
automatic function.
1. Presentation of the functions
1.1 General points
1.2 Description of the product
1
2
3
4
5
1000
2500
5000
7500
10000
OFF
LUX
10
75
150
225
300
OFF
LUX
Lux
1500 Lux
500 Lux