hager
"DALI Gateway C00Cx2" software
Parameters
Seite 116 von 130
Response at the end of
the disable function
Switch-off
Blinking
Brightness value
No change
The behaviour of the DALI group at the end
of the disable function can be
parameterized.
At the end of the disable the group will
switched off and re-enabled.
After the end of the disable, the DALI
devices of the group will be re-enabled for
the bus mode blinking on and off.
Generally, the blinking time is
parameterized for all groups on the
"General" parameter card. During blinking,
the logic switching state is "ON - 1". The
brightness reported back is the switch-on
brightness. A Soft-ON/OFF function will be
ignored during the blinking. The blinking
status will remain active until another bus
command is received or until the manual
control will provide a different status.
At the end of the disable, the group will be
adjusted to the brightness value specified
in the drop-down menu next to the
parameter. The adjustable value is
restricted by the parameterized minimum
and maximum brightness.
At the end of the disable the DALI devices
of a group will not react and keep the
current brightness value or remain
switched off. The bus mode of the group
will be re-enabled afterwards.
•
This parameter becomes visible only if