hager
"DALI Gateway C00Cx2" software
Parameters
Seite 119 von 130
Brightness for forced-
control position active,
ON
Brightness value
No change
Memory value (brightness
prior to the last shutoff)
If the forced-control position is active and a
forced switching is “ON”, the parameter will
determine the behaviour of the Group’s
DALI devices.
The group will be adjusted to the
brightness value specified in the drop-down
menu next to the parameter. The
adjustable value is restricted by the
parameterized minimum and maximum
brightness.
The DALI devices of a group will not react
and keep the current brightness value or
remain switched off.
The value will be adjusted to the brightness
value that was active and internally stored
prior to the last switch-off (via the
“Switching” or “Switching central function”
object). This memory value is permanently
stored so that the value is pre-defined to
the maximum brightness after the return of
bus or mains voltage or after programming
with the ETS.
•
This parameter becomes visible only if
the forced-control position function has
been enabled.
Response at the end of
the forced-control
position function
No change
Tracked brightness value
The response of the DALI group at the end
of the forced-control position can be
parameterized.
At the end of the forced-control position,
the DALI devices of a group will not react
and keep the current brightness value or
remain switched off. The bus mode of the
group will be re-enabled afterwards.
At the end of a forced control, the status
received or set prior to the executed
forced-control position function will be
resumed with the applicable brightness
value. If applicable, active time functions
will also be considered. The bus mode of
the group will be re-enabled afterwards.
•
This parameter becomes visible only if
the forced-control position function has