Staircase timer function (applies only to DALI groups 1...16!)
Staircase timer function
?
Yes
No
This parameter can enable the Staircase
timer function and the corresponding
communication objects.
Staircase lighting time
00:00:01 … 23:59:59
[hh:mm:ss]
2 min
This parameter is used for programming
the duration of the Staircase timer function.
•
This parameter will be visible only if the
Staircase timer function has been
enabled.
Staircase lighting time
retriggerable ?
Yes
No
An active switch-on time can be retriggered
(setting "Yes"). Alternatively, retriggering
can be suppressed (setting "No").
•
This parameter will be visible only if the
Staircase timer function has been
enabled.
Response to OFF
telegram
Switch-off
Ignore
An active switch-on time can be cancelled
prematurely by switching off the Staircase
timer function.
The staircase lighting time is cancelled if an
OFF-telegram to the "Staircase timer start /
stop" object has been received.
OFF telegrams will be ignored. The switch-
on time will be fully completed.
•
This parameter will be visible only if the
Staircase timer function has been
enabled.
Activate pre-warning
time ?
Yes
No
Once the switch-on time of a Staircase
timer function has ended, the DALI devices
of the group are able to produce a pre-
warning prior to the shutoff (brightness
reduction). The pre-warning function is
designed to warn anyone present in the
staircase that the lights will go out shortly.
The pre-warning function is activated.
The pre-warning function is deactivated.
•
This parameter will be visible only if the
Staircase timer function has been