Setting the shutoff brightness
The shutoff function requires the definition of the shutoff brightness. The shutoff brightness is set
separately for each DALI group.
The shutoff function must be enabled.
Set the “Shutoff when brightness value is smaller” parameter in the "Groups - [x] group name -
dimming" parameter node to the required brightness value.
Once a dimming operation causes a value to fall below the parameterized shutoff brightness and
once the brightness has been set to constant, the DALI group will shut off or will start the delay until
the shutoff. The selectable parameter must be within the limits of the maximum and minimum
brightness.
Setting the delay of the shutoff function
A time delay can be activated before the shutoff function will automatically shut off when falling below
the shutoff brightness at the end of a dimming operation. There is the option available to enable the
time delay separately for each DALI group.
The shutoff function must be enabled.
Configure the “Delay until shutoff ?” parameter in the "Groups - [x] group name - dimming" to “Yes“.
Once a dimming operation causes a value to fall below the parameterized shutoff brightness and
once the brightness has been set to constant, the DALI Gateway will trigger the delay time. The DALI
group will completely shut off once the delay time has lapsed. The delay time can be retriggered by
other dimming operations.