"DALI Gateway C00Cx2" software
Functional description
Seite 94 von 130
•
The “Default” button will reset all commissioning parameters. Assignments of DALI devices to groups
get lost from the project design and the DALI Gateway if the “Default” button in the commissioning
environment has been activated!
Completing the DALI commissioning
Once the required DALI devices have been assigned to the groups in the plug-in, the commissioning
can be completed. The commissioning parameters will be automatically transferred into the DALI
Gateway after completion. For this reason the plug-in will communicate with the DALI Gateway via the
ETS 3 bus connection.
The DALI Gateway must be connected to the KNX/EIB and the bus; the mains voltage must be
switched on.
The ETS 3 must have a working communication interface to the bus (e.g. RS-232 or USB).
The commissioning environment of the plug-in must be quit before the commissioning parameters
are transferred into the DALI Gateway and into the devices. Select a different parameter page in the
tree node view of the plug-in or close the plug-in by activating the “OK” button.
The synchronisation for the commissioning will now be executed. The process may take some time
and depends on the number of the created groups and the connected DALI devices. The plug-in will
program the Gateway with the group assignments first. A progress bar indicates the current progress
(cf. figure 41).
Once the group assignments have been updated in the DALI Gateway, the connected DALI devices
can now be updated as well. The Gateway communicates with the connected devices via the DALI
line programming them automatically (cf. figure 42 on the following page).
Figure 41: Synchronising the commissioning parameters between plug-in and DALI Gateway