TXE530
20
6LE001714A
Example with maximum closure set at 40%:
Sun protection operation for shutters:
If
the luminosity level is sufficient (more than 40 Klux for more than one minute)
and
the sun is shining on the facade:
-
The shutter is positioned in line with the path of the sun between 20 % closure and the maximum shading position defined
by the configuration (20 to 80 %).
If
the luminosity level is insufficient (less than 32 Klux for more than 15 minutes)
or
the sun is not shining on the facade:
-
The shutter is positioned at a fixed value of 0 %.
Example
Shutter position
Sun position - Angle between
10%
46° ... 90°
20%
31° ... 45°
30%
16° ... 30°
40%
0° ... 15°
20 %
10 %
30 %
40 %
1
2
3
4
α
1
2
3
4
Summary of Contents for TXE530
Page 66: ...TXE530 66 6LE001714A...