3.1.2.3 Wind speed

The wind speed value is mainly used to secure shutters and blinds. It can also be used as a display on touch screens.

A communication object is available for each of the three alarms.
The wind alarm (1 to 3) operates as follows:

-

The wind alarm is activated (bit = 1) if the value measured is greater than the threshold value for more than 2 seconds. It 
will immediately be transmitted and every 10 minutes thereafter.

-

The wind alarm is deactivated (bit = 0) if the value measured is less than the threshold value for more than 5 minutes. It 
will immediately be transmitted and every 10 minutes thereafter.

Parameter

Description

Value

Wind speed

The wind speed value is periodically sent every 30 
minutes and at each change if the variation is greater 
than 20 % compared to the last measurement.

Emission of value every 30 minutes

Emission on change: +/- 20 %

Wind alarm 1

wind alarm 1 (1 bit) can be used directly by the shutter/
blind output modules.

The alarm threshold is set at 4 m/s (14.4 km/h) and the 
alarm will be transmitted every 10 minutes.

Emission every 10 minutes if wind speed 
> 4 m/s

Wind alarm 2

wind alarm 2 (1 bit) can be used directly by the shutter/
blind output modules.

The alarm threshold is set at 8 m/s (28.8 km/h) and the 
alarm will be transmitted every 10 minutes.

Emission every 10 minutes if wind speed 
> 8 m/s

Wind alarm 3

wind alarm 3 (1 bit) can be used directly by the shutter/
blind output modules.

The alarm threshold is set at 12 m/s (43.2 km/h) and the 
alarm will be transmitted every 10 minutes.

Emission every 10 minutes if wind speed 
> 12 m/s

Communication objects:

1 - Wind speed - Output 

(2 Byte - 9.005 DPT_Value_Wsp)

4 - Wind alarm 1 - Output

 (1 Bit - 1.005 DPT_Alarm)

5 - Wind alarm 2 - Output

 (1 Bit - 1.005 DPT_Alarm)

6 - Wind alarm 3 - Output

 (1 Bit - 1.005 DPT_Alarm)

Summary of Contents for TXE530

Page 1: ...ware KNX GPS Weather station Electrical Mechanical characteristics see product user manual Product reference Product designation Application software ref TP device Radio device TXE530 KNX GPS Weather...

Page 2: ...1 Date and time 9 3 1 1 2 Time change 11 3 1 2 Weather data and alarms 13 3 1 2 1 Temperature measurement 14 3 1 2 2 Luminosity 14 3 1 2 3 Wind speed 15 3 1 2 4 Rain alarm 16 3 1 3 Shading 16 3 1 4 He...

Page 3: ...with ETS4 and ETS5 They can be downloaded from our website under the order number 1 2 2 Application descriptions This product can also be configured using the TXA100 configuration tool It is composed...

Page 4: ...ew presentation 2 General Description 2 1 Installation of the device Touchscreen Touchpad Smartphone Local server KNX shutter control Thermostat KNX Radio switch KNX TXE530 ETHERNET Tasks 24 V Supply...

Page 5: ...sical addressing button 6 Physical addressing LED 2 1 3 Physical addressing In order to perform the physical addressing or to check whether or not the bus is connected press the lighted push button se...

Page 6: ...the bus or auxiliary and after programming or restarting The device sends all of the actions as well as the switching outputs and statuses according to the timelines defined below The date and time a...

Page 7: ...during hail snow and minus temperatures Turbulence and upslope winds close to the weather station are also recorded This information is transmitted periodically and can be used as a wind alarm control...

Page 8: ...bient temperature of facade 1 using a master part to more accurately manage heat protection and recovery Communication objects Date slave KNX GPS Weather station Time slave Date and time slave Date an...

Page 9: ...ime source clock Date and time for Master In the first instance the current date and time can be set via the ETS The weather station works with this data until a valid GPS signal is received for the f...

Page 10: ...ally to master mode When the master device re sends the date and time the weather station returns to slave mode Date and time in Autonomous mode The weather station operates with its own date and time...

Page 11: ...arameter Description Value Summer winter time change and UTC definition The time change is carried out automatically according to the Central Europe criteria Central Europe The time change is carried...

Page 12: ...day Thursday Friday Saturday Any day Parameter Description Value After This setting determines at what time day month hour minute the change will take place Day 1 25 31 day Month 1 3 12 month Hours 0...

Page 13: ...e settings in this tab are set and cannot be modified Parameter Description Value After This setting determines at what time day month hour minute the change will take place Day 1 25 31 day Month 1 3...

Page 14: ...tion Value Outdoor temperature The temperature value is periodically sent every 30 minutes and at each change in temperature if it is greater than 0 5 C from the last measurement Emission of value eve...

Page 15: ...ared to the last measurement Emission of value every 30 minutes Emission on change 20 Wind alarm 1 wind alarm 1 1 bit can be used directly by the shutter blind output modules The alarm threshold is se...

Page 16: ...e recommend working with facades that are fitted only with shutters or only with blinds The shading control options blind or louver position and slat tilt positions are associated with facades Facade...

Page 17: ...ed in the setup for the shading function to operate correctly Defining the direction of each facade used Example 1 Example 2 Direction Facade 1 N 0 Facade 2 E 90 Facade 3 S 180 Facade 4 W 270 Directio...

Page 18: ...tion Value Facade x The facade is not used for position tracking Not active The facade is used for position tracking the rolling shutters only Position tracking for shutters The facade is used for pos...

Page 19: ...n protection that is pulled from one side to the other or pulled in front of a window from both sides Shading with roller shutters Shading is automatically controlled if the shading conditions on the...

Page 20: ...er is positioned in line with the path of the sun between 20 closure and the maximum shading position defined by the configuration 20 to 80 If the luminosity level is insufficient less than 32 Klux fo...

Page 21: ...hading conditions on the relevant facade are fulfilled luminosity threshold 40 klux and sun on the facade To limit the number of trips the shading starts by fully lowering the blinds following the dir...

Page 22: ...ct receives the value 0 sun protection of the relevant facade is authorised If the facade x shading deactivation object receives the value 1 sun protection of the relevant facade is not authorised The...

Page 23: ...ions is recommended when rooms are empty 25 Sun protection facade 3 position Output 1 Byte 5 001 DPT_Scaling 26 Sun protection facade 3 slat angle Output 1 Byte 5 001 DPT_Scaling 27 Shading facade 3 d...

Page 24: ...ufficient less than 40 Klux for more than 10 minutes or the sun is not shining on the facade or the outdoor temperature is less than 28 C and the indoor temperature is less than 25 C for facade 1 for...

Page 25: ...es as follows If the heat recovery protection deactivation object receives the value 0 the heat recovery or protection is disabled If the heat recovery protection deactivation object receives the valu...

Page 26: ...C R T 19 Shading facade 1 deactivation Input 1 bit C W 20 Shading deactivation status facade 1 Output 1 bit C R T 21 Sun protection facade 2 position Output 1 byte C R T 22 Sun protection facade 2 sla...

Page 27: ...is object sends the wind speed from the weather station on the KNX bus The wind speed value is periodically sent every 30 minutes and at each change if the variation is greater than 20 compared to the...

Page 28: ...threshold value for more than 5 minutes It will immediately be transmitted and every 10 minutes thereafter Wind alarm 1 The alarm threshold is fixed at 4 m s Wind alarm 2 The alarm threshold is fixed...

Page 29: ...when the Date and time setting has the value Slave This object receives the reference time of an external device Object value For further information see Date and time Byte 3 MSB Byte 2 Byte 1 LSB Day...

Page 30: ...s Year Binary 0 1900 to 255 2155 8 bit Year Month Binary 1 to 12 4 bit Month Day of the month Binary 1 to 31 5 bit Day Day of the week Binary 0 any day 1 Monday 7 Sunday 3 bit Hours Binary 0 to 23 5 b...

Page 31: ...e KNX bus For further information see Date and time No Name Function of the object Data type Flags 13 Date master Output 3 Byte 11 001 DPT_Date C R T This object is activated when the Date and time se...

Page 32: ...This object sends the reference time from the weather station on the KNX bus Object value For further information see Date and time Byte 3 MSB Byte 2 Byte 1 LSB Day Hours Minutes Seconds D D D T T T T...

Page 33: ...Code Value Units Year Binary 0 1900 to 255 2155 8 bit Year Month Binary 1 to 12 4 bit Month Day of the month Binary 1 to 31 5 bit Day Day of the week Binary 0 any day 1 Monday 7 Sunday 3 bit Hours Bin...

Page 34: ...has the value Position tracking for shutters or Position and slat tracking for blinds It is used for positioning the shutter or blind at the desired height in response to the value sent on the KNX bu...

Page 35: ...ation status facade 1 Output 1 Bit 1 003 DPT_Enable C R T This object is activated when the Facade 1 setting has the value Position tracking for shutters or Position and slat tracking for blinds The f...

Page 36: ...it 1 003 DPT_Enable C W See object No 19 No Name Function of the object Data type Flags 28 Shading deactivation status facade 3 Output 1 Bit 1 003 DPT_Enable C R T See object No 20 No Name Function of...

Page 37: ...at protection automatic control or Use of heat recovery automatic control setting is activated The heat recovery protection deactivation status object transmits the heat recovery protection deactivati...

Page 38: ...PT_Value_Temp C W This object is activated when the Use of heat protection automatic control or Use of heat recovery automatic control setting is activated It receives the indoor temperature which is...

Page 39: ...XE530 39 6LE001714A TXE530 Weather station Product view View of channels Product settings 4 Programming by Easy Tool 4 1 Product overview 1 Input 1 Output TXE530 1 1 Housing TXE530 1 1 Housing Shutter...

Page 40: ...end a request If there is no response the weather station switches automatically to master mode When the master device re sends the date and time the weather station returns to slave mode Date and tim...

Page 41: ...of the scan the products requiring the date and time are immediately updated A request system Date and time request was installed for automatic management of the date and time Group address Date 1 30...

Page 42: ...0 minutes thereafter Links For this function the link can be automatically established 2 ways by the presence of other compatible products by configuration Automatic links This automatic link is used...

Page 43: ...TXE530 43 6LE001714A Group address Outdoor temperature 30 0 000 Frost alarm 30 0 012 Domovea CONSUMER KNX Weather station TXE530 SUPPLIER Frost alarm...

Page 44: ...one minute fixed value The Night information is activated bit 1 if the value measured is less than the threshold value 10 Lux for one minute Links For this function the link is made automatically if c...

Page 45: ...night information the LED function must be set up in the product Note For the LED function status setting to appear a function must be defined in the corresponding input LED push button WST31x WST32x...

Page 46: ...Another possible link It is possible to use an ON OFF output outdoor lighting from the Day night function Group address Inputs Outputs TXE530 1 1 Housing TXA610 1 1 Housing Lighting Luminosity 30 0 00...

Page 47: ...tes thereafter Wind alarm 1 The alarm is activated if the wind speed 4 m s 14 4km h Wind alarm 2 The alarm is activated if the wind speed 8 m s 28 8km h Wind alarm 3 The alarm is activated if the wind...

Page 48: ...No wind alarm Wind alarm 1 Wind alarm 2 Wind alarm 3 Position on wind alarm Defines the status of the shutter output on receipt of wind alarms 1 2 or 3 Not active Up Down Wind speed 30 0 001 Wind ala...

Page 49: ...t will immediately be transmitted and every 10 minutes thereafter Links For this function the link can be automatically established 2 ways by the presence of other compatible products by configuration...

Page 50: ...larm Yes No Position on rain alarm Defines the status of the shutter output on receipt of the rain alarm Not active Up Down Rain alarm 30 0 011 Bi application output module TXA604 TXA606 TXA608 TXA610...

Page 51: ...the sun protection of each facade is recommended For U shaped buildings only 4 facades must be controlled separately insofar as several are facing the same direction To manage shading on a facade with...

Page 52: ...ed in the setup for the shading function to operate correctly Defining the direction of each facade used Example 1 Example 2 Direction Facade 1 N 0 Facade 2 E 90 Facade 3 S 180 Facade 4 W 270 Directio...

Page 53: ...l slats Parameter Description Value Facade orientation x This setting defines the direction of the facade according to the compass points N 0 NE 45 E 90 SE 135 S 180 SW 225 W 270 NW 315 All 360 Shadin...

Page 54: ...n protection that is pulled from one side to the other or pulled in front of a window from both sides Shading with roller shutters Shading is automatically controlled if the shading conditions on the...

Page 55: ...er is positioned in line with the path of the sun between 20 closure and the maximum shading position defined by the configuration 20 to 80 If the luminosity level is insufficient less than 32 Klux fo...

Page 56: ...protection at high sun elevations Shading is automatically controlled if the shading conditions on the relevant facade are fulfilled luminosity threshold 40 klux and sun on the facade To limit the num...

Page 57: ...he lowest position 100 while the shading function is activated This limits positioning movements so shading is carried out only by orienting the slats Note The value of the Max position for facade x s...

Page 58: ...is setting determines whether shading is established using the shutter position or the blind tilt Note This is intended only for blinds with horizontal slats Define the maximum shutter position for sh...

Page 59: ...shown below This link activates shading via the push button Select the facade to activate Group address Inputs Outputs WST312 1 1 Housing TXE530 1 1 Housing Shutter Position Facade 1 30 0 016 Slat po...

Page 60: ...temperature on all of the facades or the indoor temperature on the facade 1 Heat protection operation If the luminosity level is sufficient more than 40 Klux for more than one minute and the sun is sh...

Page 61: ...sity level is sufficient more than 40 Klux for more than one minute and the sun is shining on the facade and the outdoor temperature is less than 12 C and the indoor temperature is less than 22 C for...

Page 62: ...emperature of facade 1 Or Note This link is optional for this function Inputs Outputs WST322 1 15 Housing TXE530 1 1 Housing Shutter Inputs Outputs WYT62x 1 5 Housing TXE530 1 1 Housing Shutter CONSUM...

Page 63: ...done using the push button as shown below This link activates heat protection recovery Select the facade to activate Group address Inputs Outputs WST312 1 1 Housing TXE530 1 1 Housing Shutter Position...

Page 64: ...TXE530 64 6LE001714A 5 Appendix 5 1 Specifications 5 2 Characteristics Device TXE530 Max number of group addresses 254 Max number of allocations 255 Objects 37...

Page 65: ...ection facade 2 slat angle 35 Shading facade 2 deactivation 35 Shading deactivation status facade 2 36 Sun protection facade 3 position 36 Sun protection facade 3 slat angle 36 Shading facade 3 deacti...

Page 66: ...TXE530 66 6LE001714A...

Reviews: