Page 6
About Zones Inputs
Each of the 48 zone inputs on a Lumina system may be configured as a trouble, a freeze, a water, an auxiliary, an outdoor
temperature, a temperature, a temperature alarm, or a humidity input. Zones 9-16 are the only inputs that can be configured as a
PESM.
An external 1000-ohm end-of-line zone resistor is required for all zones unless the Setup item Zone Resisters is set to "No". If the
Setup item Zone Resistors is disabled, all zones will not use an end-of-line resistor. In this configuration, all zone switches must
be normally closed. If any zone requires a normally open switch, the Setup item Zone Resistors must be set to "Yes" and all
zones will require and external 1000-ohm end-of-line resistor.
The zone type for each zone is selected through the Lumina Setup menu or by using the PC Access software.
The system supports a maximum zone resistance, excluding the end-of-line resistor, of 150 ohms. The default setting for Zone
Resistors is "Yes". The default settings for all zone inputs on a Lumina controller are configured as Auxiliary inputs.
Lumina can be expanded to 48 zones by adding two 16 Zone Hardwire Expander Modules a Wireless Receiver.
Zone Hookups
The Lumina system supports both normally open and normally closed switches. An external 1000-ohm end-of-line resistor must
be used for all burglary zones if ZONE RESISTORS is set to "Yes".
1.
When using a normally open switch, a 1000-ohm end-of-line resistor must be in parallel with the zone being used. Maximum
loop resistance excluding end-of-line resistor should not exceed 150 ohms. ZONE RESISTORS must be set to "Yes".
2.
When using a normally closed switch, a 1000-ohm end-of-line resistor must be put in series with the zone being used if Zone
Resistors are set to "Yes". If Zone Resistors are set to "No", the 1000-ohm end-of-line resistor is not used. Maximum loop
resistance excluding end-of-line resistor should not exceed 150 ohms.
3.
Power devices from AUXILIARY 12V.
4.
Unused zones may be left open, and should be left at the default setting of Auxiliary zone types.
About Outputs
The Lumina provides 8 hardwired voltage outputs. Outputs 1 - 8
can supply a
maximum
of 100 mA each. These outputs are
included in the total DEVICES load, which cannot exceed 1A.
The Lumina has 2 additional outputs labeled INT HORN and EXT HORN that can supply a
maximum
of 1A, split between the
two outputs. Theses outputs are fused separately from Outputs 1 – 8.
General Purpose Switching Applications
Voltage outputs will supply 12 VDC to the output terminal when its corresponding unit is ON. Output 1 is designated Unit 65
through Output 8 which is Unit 72. This can be used to drive relays for many different applications, including switching sprinkler
valves and low-voltage lighting.
Unit Number 73 is used to control the output labeled INT HORN and Unit Number 74 is used to control the output labeled EXT
HORN.