Page 84
Zone Response Time
All zones, in the Lumina are set to a 300 millisecond fixed response time.
Zone Types
ZONE TYPE
NUMBER
DESCRIPTION
TROUBLE
49
Trouble
FREEZE 54
Freeze
WATER
55
Water
AUXILIARY
64
Auxiliary
ENERGY
SAVER 80
Programmable
Energy
Saver
Module
OUTDOOR
TMP
81
Outdoor
Temperature
TEMPERATURE 82
Temperature
TEMP
ALARM
83
Temperature
Alarm
HUMIDITY
84
Humidity
ER OUTDOOR TMP
85
Extended Range Outdoor Temperature
ER TEMPERATURE
86
Extended Range Temperature
ER TEMP ALARM
87
Extended Range Temperature Alarm
TROUBLE
This zone type can be used to monitor the status of an external device, such as the battery status of a wireless receiver or the HAI
Touchscreen Hub. It can also used to record events in the event log (i.e. driveway activation, opening of a gate, etc.).
When the zone is tripped, the zone name will be displayed on the display as "NOT RDY". The trouble is logged in the event log.
The voice dialer will not be activated.
FREEZE
This FREEZE zone type will generate an alarm (keypad beeper) and will use the voice dialer to dial out.
WATER
This WATER zone type will generate an alarm (keypad beeper) and will use the voice dialer to dial out.
AUXILIARY
A zone defined as AUXILIARY is used to activate macros or used as conditionals in programs. This is the default setting for all
zones. Zones that are not in use should be configured as Auxiliary.
PROGRAMMABLE ENERGY SAVER MODULE
This zone type is for use with the Programmable Energy Saver Modules (PESM). It converts the Zone and the corresponding
Voltage Output to operate the PESM. Only Zones 9-16 and 49-176 can be programmed as a PESM.
OUTDOOR TEMPERATURE AND ER OUTDOOR TEMPERATURE
Use this zone type for Outdoor Temperature Sensors. The outdoor temperature can be displayed on the keypad, spoken over the
telephone, or displayed on an HAI Communicating Thermostat.
TEMPERATURE AND EXTENDED RANGE TERMPERATURE
The general-purpose TEMPERATURE zone type is typically used to monitor indoor temperatures and control devices. It sets the
zone secure/not ready state for program conditionals and event button activated programs.
If Freeze Alarm is enabled, it reports a potential freeze condition if the temperature falls below 40
o
.