Page 46
NOTE:
If VERIFY FIRE ALARMS is turned ON,
any
device (other than FIRE or GAS) connected to a SWITCH 12V Output (i.e.
Glassbreak Detectors), must be connected to a zone configured as a LATCHING ZONE TYPE.
This feature is designed to reduce false alarms and is turned ON by factory default. The following notice is required by UL:
WARNING
This unit includes an alarm verification feature that will result in a delay of the system fire alarm signal from the initiating
circuit. The total delay (Omni II controller plus detector delay) shall not exceed 60 seconds. No other initiating devices shall
be connected to these circuits unless approved by the local authority having jurisdiction.
Zone Control Detector Total Delay
Circuit Unit Delay Model/Delay
________ : 10 seconds + ______________ = __________________
________ : 10 seconds + ______________ = __________________
________ : 10 seconds + ______________ = __________________
________ : 10 seconds + ______________ = __________________
SUPERVISE INT SNDR
This enables or disables supervision of the Interior Horn Output, which monitors the wiring to the connected sirens. Factory
default is disabled.
SUPERVISE INT SNDR: 0
0=NO 1=YES
↕
SUPERVISE EXT SNDR
This enables or disables supervision of the Exterior Horn Output, which monitors the wiring to the connected sirens. Factory
default is disabled.
SUPERVISE EXT SNDR: 0
0=NO 1=YES
↕
ENABLE EMERGENCY KEYS
This enables or disables the functionality of the emergency keys on the console keypad. Factory default is enabled. Select the 1
(YES) key to enable the emergency keys. Select the 2 (NO) key to disable the emergency keys.
ENABLE EMERG KEYS: 1
0=NO 1=YES
↕
TIME DISPLAY
This allows you to choose between AM/PM and 24-HOUR time format.
TIME DISPLAY: 1
1=AM/PM 2=24HR
↕