Page 29
5.
Record the owner's NAME and ADDRESS in the ADDRESS speech memory as shown in SETUP ADDRESS in the
OWNER'S MANUAL (Press 8, 9, then 1111 or the current Master code to record the address).
NOTE: DO NOT record any TOUCH TONES in the ADDRESS!!
6.
Check that all in-house phones are working.
BURGLAR ZONE CHECK OUT
1.
With all doors and windows closed and all motion detectors and security devices secure, the console display should read
"SYSTEM OK".
2.
If any zones are abnormal, check your wiring. If the battery indication is low, make sure that the battery is connected
securely. Give the battery a chance to charge.
3.
From the top-level display, have a partner go around the house and trip each sensor one at a time. The display should
indicate the correct zone "NOT RDY" when the zone is tripped, then return to "SYSTEM OK" when the zone is secured. Be
sure that the zone type indicated (ENTRY/EXIT, PERIMETER, ETC.) is correct for the zone being tested.
4.
If the zone being checked is armed, (i.e. PANIC or TAMPER type, which is always armed) the alarm will be activated. Press
OFF and 1111 or the current User code to silence the alarm, or bypass the PANIC and TAMPER zone(s) before you start.
5.
Reconnect the sirens. Be sure that no one is standing near a siren. Activate the alarm, and ensure that both the inside and,
after a delay, outside sirens activate.
FIRE ZONE CHECK OUT
1.
Press ' * ' to return the console to the SYSTEM OK indication. Check the fire zone per the sensor manufacturer's
instructions. The fire alarm should be activated (pulsing interior sounder, exterior siren).
2.
Press ' * ' to silence the alarm. The display will still indicate that the FIRE ZONE is in alarm.
3.
Press DAY or NIGHT or AWAY and the User code to arm the system, then OFF and the User code to disarm. This
arm/disarm cycle will reset the smoke detector. If the cause for alarm (i.e. smoke) has cleared, the display will return to
SYSTEM OK.
NOTE: Be sure that the DIAL OUT DELAY is long enough so that you can cancel the alarm before the system dials out.
HOME CONTROL CHECKOUT
1.
Confirm that the HOUSE CODE on the OmniPro II is set to the same HOUSE CODE set on all of the modules (See SETUP
CONTROL).
2.
On the console press 4, 1 (ALL ON). All lamp type modules should go on. Note that some modules, such as appliance
modules, voltage outputs, and flags do not respond to ALL ON.
3.
On the console press 4, 2 (ALL OFF). All modules should go off. Note that voltage outputs and flags do not respond to ALL
OFF.
4.
Operate each unit number individually and verify that it works.
5.
Ensure that all inputs and outputs are working.
Summary of Contents for Omni Pro II
Page 2: ......
Page 21: ...Page 15 BLACK RED RED FIGURE 7 SOUNDER CONNECTIONS...
Page 71: ......
Page 72: ...HAI New Orleans LA U S A...