Page 36
For output types, the current setting is shown on the bottom line. Press the ' # ' key to select a new type from a list of types. The
display shows:
SELECT TYPE: 6
INT SNDR
↕
Use the Up and Down arrow keys to scroll through the list, or select the appropriate output type number. Then press ' # ' to enter
the new type.
If the Interior Horn is configured as a "General Purpose" output, Unit Number 393 is used to control the output. If the Exterior
Horn is configured as a "General Purpose" output, Unit Number 394 is used to control the output. In this configuration, Unit
Numbers 393 and 394 should not be used as "Flags".
SETUP ZONES
To configure zone expansion and the zone type for each security zone, from the Installer Setup menu, select the 2 (ZONE) key.
ZONE EXPANSION
Expansion Enclosures can be used to add additional zones to the OmniPro II system. Each Expansion Enclosure adds 16 zones to
the system. If used, you must specify the number of Expansion Enclosures (1-8) used.
Each Model 17A00 Expansion Enclosure adds 16 hardwired zones to the OmniPro II system.
Wireless Receives can also be used to add additional zones to the OmniPro II system. When connected to an OmniPro II, the
Wireless Receiver is recognized as an Expansion Enclosure. Each Wireless Receiver can handle up to 64 wireless zones, in
groups of 16. Each group of 16 zones is considered 1 Expansion Enclosure. You must specify how many groups of wireless
zones are being used.
Specify the number of 17A00 Expansion Enclosures plus the number of wireless groups:
NUMBER OF EXP ENCL 0
1-8
↕
NOTES:
1.
Up to 2 Model 10A06 Hardwire Expanders can be used with OmniPro II. Zones 1-16 on the first Expander are Zones 17-32
on OmniPro II. Zones 1-16 on the second Expander are Zones 33-48 on OmniPro II.
2.
When used, the Model 10A06 Hardwire Expander Modules must be configured under Setup | Installer | Expansion.
3.
Zones 1-16 on the first Expansion Enclosure are Zones 49-64 on OmniPro II. Zones 1-16 on the 2nd - 8th Expansion
Enclosure are Zones 65 -176, respectively on OmniPro II.
ZONE RESISTORS
This item is used to specify if the 1000-ohm end-of-line zone resistors will be used with zone inputs on the controller and zone
expanders (this does not affect Expansion Enclosures). If this item is set to "Yes", all zones are required to use an end-of-line
resistor.
End-of-line zone resistors are always required on Supervised Fire and Gas zones, and all zone inputs on Expansion Enclosures.
The default setting is "Yes".
ZONE RESISTORS: 1
0=NO 1=YES
↕