Page 32
OUTPUT TYPE
NUMBER
DESCRIPTION
GENERAL PURPOSE
0
General Purpose Output
OK TO ARM
1
OK To Arm
ARMED
2
Armed
PRE-ALM SNDR
3
Pre-Alarm Sounder
INT SNDR
4
Interior Sounder
INT BURG SNDR
5
Interior Burglary Sounder
INT FIRE SNDR
6
Interior Fire Sounder
EXT SNDR
7
Exterior Sounder
EXT BURG SNDR
8
Exterior Burglary Sounder
EXT FIRE SNDR
9
Exterior Fire Sounder
BURG COMM
10
Burglary Communicator
FIRE COMM
11
Fire Communicator
AUX COMM
12
Auxiliary Communicator
SWITCHED POWER
13
Switched Power Output
For output types, the current setting is shown on the bottom line. Press the ' # ' key to select a new type from a list of output
types. The display shows:
SELECT TYPE: 6
INT SNDR
↕
Use the arrow keys to scroll through the list, or select the appropriate output type number. Then press ' # ' to enter the new type.
SETUP ZONES
To setup the zone type for each security zone, from the Installer Setup menu, select the 2 (ZONE) key.
WIRELESS RECEIVER
A Wireless Receiver can be used to add 16 zones (9-24) to the OmniLT. If used, you must enable the following item:
WIRELESS RECEIVER: 0
0=NO 1=YES
↓
NOTES:
1.
If the Model 22A00 Expansion Module is used, if must be configured under Setup | Installer | Expansion.
2.
If a Wireless Receiver is used and the 22A00 Expansion Module is also connected, all 16 zones (9-24) will be wireless zones.
Outputs 1-8 (Units 17-24) on the Expansion Module may be used; however the zones will be inactivated.
ZONE RESISTORS
This item is used to specify if the 1000-ohm end-of-line zone resistors will be used with zone inputs other than Supervised Fire
and Gas. If this item is set to "Yes", all zones will require an end-of-line resistor. The default setting is "Yes".
ZONE RESISTORS: 1
0=NO 1=YES
↕
Z 1 TYPE THROUGH Z 25 TYPE
This item specifies the zone type for each zone.
ZONE 1 TYPE: 64
AUXILIARY #=CHNG
↕
THROUGH
ZONE 25 TYPE: 64
AUXILIARY #=CHNG
↑