Page 37
COMMUNICATOR TYPE
This item is used to select the transmitting parameters of the digital communicator. The OmniLT can transmit in FAST 2300 Hz
(20 PPS) mode, in SLOW 1400 Hz (10 PPS) 3/1 format, and in Contact ID.
COMMUNICATOR TYPE: 2
0=2300 1=1400 2=ID
↕
The default setting is 2 = ID (Contact ID). If you need to transmit to a 4/2 or 3/1 receiver, select the proper handshaking
frequency (2300 Hz or 1400 Hz) and press ' # '.
TWO-WAY AUDIO
If a Two-Way Audio Module is being used, this item enables hands free audio communication between your customer's premises
and the central station. After the transmission of the alarm to the central station, the operator can talk and listen to people and
sounds at the premises.
TWO-WAY AUDIO: 0
0=NO 1=YES
↕
If a Two-Way Audio Module is part of the system, select the 1 (YES) key to enable this feature.
REPORT OPEN/CLOSE
The communicator can be setup to send an opening and a closing report by user code. Whenever the system is disarmed the
communicator will send an opening report to the central station. When the system is armed, the communicator will send a closing
report to the central station.
REPORT OPEN/CLOSE: 0
0=NO 1=YES
↕
To enable the communicator to send opening and closing reports to the central station, select the 1 (YES) key.
AUTOMATIC TEST TIME
The communicator CAN be setup to automatically send a test code to the central station on a periodic basis. AUTOMATIC
TEST TIME is used to set the time and days of the week of the test, and the TEST CODE specifies the code that will be
transmitted for the test.
AUTOMATIC TEST TIME:
-- NEVER #=CHNG
↕
To disable the automatic test, press the ' # ' key and then 0 for Never, and ' # '. If you are using PC Access, deselect all days under
the heading "Test time".
When using a 4/2 or 3/1 format, the digital communicator will send the designated Test Code. The default Test Code is 98.
TEST CODE: 98
0-FF
↕
ALARM CODES (4/2 and 3/1 Formats)
Press the down arrow (
"
) to advance to the next ZONE ALARM CODE. Press the up arrow (
!
) to go to the previous ZONE
ALARM CODE. To change an alarm code, enter two digits for 4/2 format, or one digit when using 3/1 format, then press ' # '.
Enter the 2 digit alarm code (1 digits if using 3/1 format) and press ' # '. To enter the digits B-F, first press the OFF key, then
press the 1-5 key respectively (i.e. B1 = OFF 1 1 # and CB = OFF 2 OFF 1 #).
The various alarm codes are sent when the indicated alarm zone is tripped. Each alarm code must be two digits long for 4/2
format (01-FF), 1 digit for 3/1 format (1-F).