DIAL OUT DELAY
The DIAL OUT DELAY is the number of seconds that the OmniLT waits before making an emergency dial out, AFTER the
alarm is "tripped" (activated by burglar or fire). This delay is set at the factory to 15 seconds. We recommend a minimum time
of 15 seconds to preclude an accidental activation of the alarm from calling in a false alarm.
DIAL OUT DELAY: 15
0-60 SECONDS
↕
ALARM RESET TIME
The Alarm Reset Time is the time it takes before the alarm system resets itself after the alarm is tripped.
ALARM RESET TIME: 4
1-30 MINUTES
↕
To change the alarm reset time, enter a new time between 1-30 minutes, then press the ' # ' key. The default setting is 4 minutes.
ARMING CONFIRMATION
The Arming Confirmation is a quick pulse (squawk) given by the exterior siren when the alarm system is armed into a security
mode and the EXIT DELAY is expired.
ARMING CONFIRMATION: 0
0=NO 1=YES
↕
To enable the arming confirmation feature, press the 1 (YES) key, then press the ' # ' key. The default setting is disabled.
FIRE ALARM VERIFICATION
This unit is equipped with a FIRE ALARM VERIFICATION feature. When a zone configured as a FIRE (Type 32) or a GAS
(Type 34) is activated, the system will cycle the SWITCH 12V Output off for 10 seconds. The SWITCH 12V Output will then be
restored, and 5 seconds later, the zones will be monitored again. If the zone is activated again within a 2-minute window, the fire
alarm will be activated. If not, no fire alarm will be indicated.
VERIFY FIRE ALARMS: 1
0=NO 1=YES
↕
NOTE:
If VERIFY FIRE ALARMS is turned ON,
any
device (other than FIRE or GAS) connected to a SWITCH 12V Output (i.e.
Glassbreak Detectors), must be connected to a zone configured as a LATCHING ZONE TYPE.
This feature is designed to reduce false alarms and is turned ON by factory default. The following notice is required by UL:
WARNING
This unit includes an alarm verification feature that will result in a delay of the system fire alarm signal from the initiating
circuit. The total delay (OmniLT controller plus detector delay) shall not exceed 60 seconds. No other initiating devices shall
be connected to these circuits unless approved by the local authority having jurisdiction.
Zone Control Detector Total Delay
Circuit Unit Delay Model/Delay
________ : 10 seconds + ______________ = __________________
________ : 10 seconds + ______________ = __________________
________ : 10 seconds + ______________ = __________________
________ : 10 seconds + ______________ = __________________