Page 17
BELL OUTPUT
The Bell Output provides 12VDC to power bells, piezo sirens, self-contained sirens, and siren drivers (do not connect speakers to
the Bell Output). Sounders can draw up to 1 amp
MAXIMUM
- (See Specifications for UL Ratings).
1.
Locate interior sounders in a central location. The sounder is very loud. Do not install it in a room where small children or
animals could be trapped if the alarm is activated. Note that the Bell Output defaults to an Interior Sounder Output Type.
2.
The Bell Output monitors the wiring to bells and sirens. It will report trouble if an open, short, or other wiring problem is
detected in the supervised bell circuit. It will also make a digital dial out when violated.
3.
For UL Listed residential fire alarm applications, the UL Listed Wheelock Model MT-12/24-R Multitone Signal or
equivalent must be used, and the "SUPERVISE BELL" feature must be set to "ON".
4.
Refer to
FIGURE 7 (BELL CONNECTION)
for connections.
RE
D
BL
AC
K
FIGURE 7 - BELL CONNECTIONS