05 Cool setpoint limit
This item is used to limit the temperature setting in cool mode. The
desired cool setting can never be set below this setting.
The default setting is 51.
06 Heat setpoint limit
This item is used to limit the temperature setting in heat mode. The
desired heat setting can never be set above this setting.
The default setting is 91.
07 Not used
08 Not used
09 Cooling anticipator
This item adjusts the tendency of the thermostat to run the cooling
system to refresh and dehumidify the air before the temperature rises
to the desired cool setting. A setting of 0 will disable this feature.
0
No anticipation
3-5
Normal anticipation
10
Maximum anticipation
The recommended setting for most forced air cooling systems is 4. A
lower number will decrease the tendency to run the cooling system
below the cooling setting. A lower setting of 2 or 3 may be desired in
dry climates.
The default setting is 4.
10 Heating anticipator
This item adjusts the tendency of the thermostat to turn the heating
unit off before the desired heat setting is reached. This is done to
avoid overheating the air while the walls and furniture catch up.
13