12 Heating minimum on/off time (minutes)
Same as Cooling minimum on/off time, for the heating system.
The default setting is 5.
13 Not used
14 Clock adjust
If the clock on the thermostat is running faster or slower than the
actual time, you can have the thermostat automatically compensate up
to 29 seconds per day. The thermostat will add or subtract the
selected amount of time daily.
(1 = - 29 to 59 = + 29 - Seconds per day - 30 = No change)
The default setting is 30.
Note: If an HAI automation system is being used, the controller
system time is sent to the thermostat every minute. This adjustment
will have no effect.
15 Filter reminder
The thermostat logs the amount of time the system fan has been
running. When this setting reaches 0, the thermostat will display a
reminder to replace the filter. The setting is the amount of days (24
hours of system operation) before this reminder is displayed.
Days - Counting down from 15 - 0
The filter reminder can be disabled by setting this item to 60.
16 System runtime (This week)
This item logs the amount of time (hours) that the heating and
cooling system was in operation this week.
17 System runtime (Last week)
This item logs the amount of time (hours) that the heating and
cooling system was in operation last week.
15