9.19: Cross Zoning (for future use)
Cross Zoning is a future option that is not available in the current firmware. The default
setting for this option is disabled.
Haibrain
recommends that you do not change this
setting.
9.20: Verified Fire
The Verified Fire feature is an option that is designed to delay Fire alarm reports to the
monitoring station until the alarm condition has been verified. Local Fire alarm indication
is not affected by this option and the control panel shall sound the siren instantly on
receiving an alarm from a smoke detector. You can program a Verified Fire timeout of
between 00 and 60 seconds (00 = disabled).
If the Verified Fire feature is enabled, a Fire alarm event shall be reported if…
x
An alarm occurs from a Fire zone and the alarm has not been restored by the
end of the Verified Fire timeout – in this case, the alarm is reported at the end of
the Verified Fire timeout.
x
An alarm occurs from a Fire zone, the alarm is restored and then a second
alarm occurs from the same zone during the Verified Fire timeout – in this case,
the alarm is reported immediately on receiving the second alarm.
x
An alarm occurs from a Fire zone and a second alarm occurs from an additional
fire zone within the Verified Fire timeout – in this case, the alarm is reported
immediately on receiving the second alarm.
To program the Verified Fire timeout:
1.
From the Programming menu, select System Options, Verified Fire [9420].
2.
Enter a value between 00 and 60 seconds (00 = disabled).
3.
Press
3
when the desired setting is displayed.
9.21: Battery Type
The battery type shall be defined according to the battery supplied with the
system (for example, if the battery sticker reads 1500 mAh, choose 1.5 Ah, if
3000 mAh, choose 3.0 Ah)
To program the battery type:
1.
From the Programming menu, select System Options, Battery Type [9421].
2.
Select the battery type.
3.
Press
3
when the desired setting is displayed.
ProGuard800™
-65-