.3.5 IPM protection
Outdoor display
LED1
flash
2
times
Method of
IPM protection is detected by checking the compressor running condition and so on
Malfunction
Detection
Malfunction
Ŷ
The system leads to IPM protection due to over current
Decision
Ŷ
The compressor faulty leads to IPM protection
Conditions
Ŷ
circuit component of IPM is broken and led to IPM protection
Supposed
Ŷ
IPM protection dues to the compressor faulty
Causes
Ŷ
IPM protection dues to faulty PCB of IPM module
Ŷ
Compressor wiring disconnected
Troubleshooting
* Caution
Be sure to turn off power switch before connect or disconnect connector, or
else parts damage may be occurred.
Turn on the unit.
whether the error is displayed before
compressor start?
The power module is fault,
need replaced
1
ǃ
The system may have been over or under charged with gas, which can be judged through the pressure of the
measuring system.
2
ǃ
The shaft of compressor is seized and the compressor needs replacing.
YES
NO
The
compressor
is
started
normally,
but
malfunctions are reported after it has run for a
while.
Seivice diagnosis
Domestic air conditioner
38