Single Split
28
3.2 AUTO mode control
(
1) When entering AUTO for the first time, the unit will select the running mode due to the below
conditions, then perform the selected mode.
Tr≥Ts-3
℃
select COOL mode (includes FAN mode)
Tr
<
Ts-3
℃
select HEAT or FAN mode
(2) After entering the AUTO mode, the mode can change over among COOL, HEAT or FAN modes
according to the indoor ambient temperature (conversion temperature difference is ±3
℃
).
(3) If the unit is in COOL mode, when it arrives compressor-stop temperature, the compressor will
stop; after compressor stops for 15 minutes, the unit will check the room temperature, if Tr
<
Ts-3
℃
,
the unit will enter HEAT or FAN mode, or the unit will still be in COOL mode;
(4) For the heat pump unit, if the unit is in HEAT mode at present, when it arrives compressor-stop
temperature, the compressor will stop; after the compressor stops for 15 minutes, the unit will check
the room temperature, if Tr
>
Ts+3
℃
, the unit will enter COOL mode, or it will still be in HEAT
mode.
(5) For cooling only unit, if the unit is at FAN mode, if Tr
>
Ts+3
℃
, the unit will enter COOL mode.
(6) When the unit is in HEAT mode, if indoor heat exchanger temperature rises up to over 63
℃
,
the unit will change into COOL mode. And within 1 hour, the heat exchanger temperature will not be
limited, the heating operation will stop temporarily. 1 hour later, the unit will select the proper mode
due to the above condition.
3.3 COOL mode control
(1) 4-way valve being powered off, compressor run/stop will depends on the temperature difference
between the room temperature at present and the set temperature.
(2) In cooling mode, every time the compressor starts up(thermostat ON), within 6 minutes, the
compressor will not be limited by the temperature sensor, but the set temperature change, shutoff
signal and protection action will not be limited by 6-minute protection, and the compressor can stop
immediately.
(3) ΔT≥1 compressor will run; ΔT≤-1 compressor will stop; -1<ΔT<1 compressor will stay in original
state.
(4) Anti-freeze protection (invalid in compulsory operation, trial running, heating mode)
Indoor coil temperature Tg≥15
℃
, outdoor motor run in compulsory HIGH and resume to normal
HIGH when Tg<13
℃
. Indoor coil temperature Tg
<
5
℃
, outdoor motor run in compulsory LOW
and resume to normal HIGH when Tg>7
℃
. Outdoor motor run in normal HIGH when 5
℃
≤Tg
<
15
℃
.
When the unit has run for over 6 minutes after compressor starts up, if indoor coil temperature
Tg<1
℃
and lasts for 1 minute, the compressor and the outdoor motor will stop, and the unit will
change to FAN mode; 9 minutes later after compressor stops and when indoor coil temperature rises
to 10
℃
, the unit will resume to COOL mode, the compressor and the outdoor motor will run again.
(5) Temperature cutoff protection
In cooling mode, the unit will check indoor coil temperature every time the compressor start and has
run for 5 minutes, when indoor coil temperature Tg > Tr
+
5, the unit will stop and 3 minutes later
restart up; if the temperature cutoff occurs for 3 times continuously, the unit will stop and alarm.
3.4 DRY mode control
(1) When the uint enters DRY mode for the first time, the compressor, outdoor motor and indoor
motor will perform according to the below conditions:
Summary of Contents for 1U48IN1EAB
Page 8: ...Single Split 6 5 Installation 1 2 1 2 3 4 1 2 1 2 3 4 2 ...
Page 9: ...Single Split 7 ...
Page 10: ...Single Split 8 ...
Page 11: ...Single Split 9 ...
Page 12: ...Single Split 10 ...
Page 13: ...Single Split 11 ...
Page 14: ...Single Split 12 ...
Page 15: ...Single Split 13 ...
Page 16: ...Single Split 14 pipe direction Right Left Rear Bottom Indoor outdoor unit connection ...
Page 27: ...Single Split 25 8 PCB photo Indoor PCB 0010451850 ...