(3) Install a suspending bolt

To support the unit weight ,anchor bolt should be used in the case of
already exists ceiling. Fow new ceiling, use flush-in type bolt, built-in
type bolt or parts pretared in the field.
Before going on installing, adjust space to ceiling.

3. Installation of indoor unit

In case of no ceiling

Install unit temporally

Put suspending bracket on the suspending bolt to hang the unit up. Be sure to use nut and
washer at both end of the breaket to secure firmly.

After installation on the ceiling

(1) Adjust unit to its right position (Refer to preparation for installation-(1))

(2)Check that unit is horzontal.

Put suspending bracket on the suspending bolt to hang the
unit up.Be sure to use nut and washer at both end of the
bracket to secure it firmly.

Water pump and floating switch is installed inside indoor unit,check four corners of the unit for
its lever using horizontal comparator or PVC tube with water.(If unit is tilting against the direction
of water drainage,problem may occur on floating water leakage.)

In the case of ceiling already exists

(1)Install unit temporally

(2)Adjust the height and position of the unit.

(3)Proceed with procedure (4) of " In the case of no ceiling "

Nut (Prepare in feild)

Washer (Prepared in feild)

Suspending bolts

Fasten (double nuts)

Insert

Washer fixing pad

(prepared in feild)

[ secure the washer firmly]

leveler

Polythene pipe

Note: All the above mentioned parts shall be prepared in feild,
the diameter of suspending bolt is M10

<Installation Example>

Ceiling

Roof

Anchor bolt

Long nut or thread

Suspending bilt M10

50 ~150mm

Installation Procedures

Summary of Contents for AB092XCERA

Page 1: ...IES ROOMAIR CONDITIONER OPERATION INSTALLATION MANUAL AB092XCERA AB122XCERA AB142XCERA AB182XCERA Please read this manual carefully before usingthis air conditioner Please keep this manual safely for future use CASSETTE TYPE INDOOR UNITS ...

Page 2: ... Points of Operation Parts and Functions Safety Cautions Maintenance When Trouble Happens Customer Need to know Installation Procedures Instructions to installation Trouble Shooting 1 2 3 4 5 6 7 8 9 10 11 12 17 18 19 20 22 ...

Page 3: ... of an old air conditioner and contact your local authority or your dealer if you have any question Please ensure that the pipework of your air conditioner does not get damaged prior to being picked up by the relevant waste disposal center and contribute to environmental awareness by insisting on an appropriate anti pollution method of disposal Disposal of the packaging of your new air conditioner...

Page 4: ...proof 1 Applicable ambient temperature range The machine is adaptive in following situation 2 If the supply cord is damaged it must be replaced by the service agent or a similar qualified person 3 If the fuse on PC board is broken please change it with the type of T3 15A 250VAC Cautions Cooling Heating Indoor outdoor Rated Maximum Minimum 27 32 18 19 23 14 35 43 10 24 26 6 20 27 15 14 5 7 24 15 6 ...

Page 5: ... lower when the room temperature close to the setting temperature in cooling mode In heating mode the compressor stops when the room temperature at setting temperature and fan turns into low speed or stops In Dry mode fan speed will be automatically varied Remote Control There is a telecommunication interface for remote control on the control panel of the indoor unit After the peripheral equipment...

Page 6: ...ly occurs while the air conditioner is working it will resume the previous working state when the power is supplied again Setting Method When the remote controller is on excluding timer mode and fan mode press the ìsleepingî button on the remote controller 10 times within 5 seconds and after the buzzer rings 4 times the air conditioner will enter the state of power failure compenstation Cancel Met...

Page 7: ...5 Parts and Functions Swing louver Air flow direction can be adjusted by using the SWING button on the remote controller Air Inlet Grille Air Filter Inside of the Inlet Grille Operating Control Panel ...

Page 8: ...ling method When need maintenance and repair call dealer to handle it Donít put figures or any other things into the inlet outlet and swing louver while the conditi oner is in operation Call the dealer to take measures to prevent the refrigerant from leaking Switch off In such case to continue using the air conditioner will damage the conditioner and may cause electrical shock or fire hazard Incor...

Page 9: ...nditioner should be cleaned only after power supply is cut off to keep from shock or hurt Otherwise may cause shock Connect earthing wire Earthing wire should not be connected to the gas pipe water pipe lightning rod or phone line incorrect earthing may cause shock Use discharge pipe correctly to ensure efficient discharge In correct pipe usage may cause water leaking Air conditioner canít be be i...

Page 10: ...gent or neutral soapy water if the air filter is too dirty Then rinse the air filter with water and reinstall after drying Caution Do not clean the air filter with hot water over 40 C otherwise may damage the filter Sweep the filter carefully Clean indoor outdoor unit Clean with hot wet cloth and neutral detergent then wipe with dry cloth Do not use too hot water over 40 C which may result in fadi...

Page 11: ...son Care See that there is no obstacle blocking the air inlet and air outlet of both indoor and outdoor unit to avoid reduce the working efficiency Be sure to install the air filter ensure that the air filter is not dirty Otherwise may result in machine damages or cause malfunciton due th dust inside the unit To protect compressor when start in HEAT mode please cut in the power supply switch 12 ho...

Page 12: ...sources in the room Sunlight direct into the room Too crowed in the room Cooled air blown out when heating When the air conditioner does not operate properly after you have checked the above mentioned items or when following phenomenon is observed stop the operation of the air conditioner and contact your sales dealer The fuse or breaker often shuts down Water drops off during cooling or drying op...

Page 13: ...After installation please use the air conditioner according to the specification in the operation manual Using Directions Adjust suitable airflow direction Avoid direct sunlight and airflow Keep the proper indoor temperature Too cool or hot is not good for your health Furthermore it will result in excessive consumption of electric power Optimal temper ature Effectively use timer Using TIMER mode y...

Page 14: ...ntenance 9 Place more than 1m away from television and radio to avoid disturbing television and radio 10 Easy for maintenance 2 Installation Preparation 1 Position of ceiling opening between unit and suspending bolt front view of unit 2 Prepare all piping refrigerant water drainage and wires connection wire of remote controller indoor unit connection wires to the indoor unit before installation in...

Page 15: ...ure to use nut and washer at both end of the bracket to secure it firmly Water pump and floating switch is installed inside indoor unit check four corners of the unit for its lever using horizontal comparator or PVC tube with water If unit is tilting against the direction of water drainage problem may occur on floating water leakage In the case of ceiling already exists 1 Install unit temporally 2...

Page 16: ...insulation Insulate drainage hose in the room 5 Cautions for the water drainage lifting pipe Installation height of water drainage lifting pipe shall be less than 280mm There should be a right angle with unit 300mm from unit Note The slope of water drainage hose shall be within 75mm make the drainage plug not to bear excessive force If several water hoses join together of as per following procedur...

Page 17: ...3 First fix it with screws temporally 4 Fasten the two temporally fixing screws and other two and tighten the four screws 5 Connect the wires of swing motor 6 Connect the wire of signal 7 If no response of remote controller check whether the wiring is correct restart remote controller 10 seconds after shut off power supply Limits of panel board installation 1 Install the panel board in the directi...

Page 18: ...pipe and liquid pipe shall be heat insulation No leakage in the flare 3 Piping connection Connecting method Spanner Spanner Joint Nut If not aligned tighten the nut by force will damage the nut that result in gas leakage The maximum length is 20m The maximum drop height is 10m Toensuretheefficiency Pipesshallbeasshortaspossible Fit the nut on and fasten AB092XCERA AB122XCERA AB142XCERA AB182XCERA ...

Page 19: ...es and the power cabes should be at least 50mm C B A Q P 1 L 2 N 2 N 1 L P Q A B C L N C1 C2 In case of using wired controller To other indoor unit To wired controller To outdoor unit L N Ring Terminal Installation Procedures 1 Incorrect address setting will cause abnormal to the system 2 Communication cable must be use sheilded type 3 Communication cable and power cable must be use ring terminal ...

Page 20: ...ntroller the times you press it stands for the address you want to set detailed as following Press button SLEEP once the address is 1 and the TIMER LED flashes once Press button SLEEP twice the address is 2 and theTIMER LED flashes twice Press button SLEEP three times the address is 3 and the TIMER LED flashes three times Press button SLEEP four times the address is 4 and the TIMER LED flashes fou...

Page 21: ...ndoor buzzer sounds 2 times that show temp compensatoin works Swith on the unit in heating mode by the remote controller press the time button to set the set temp compensatoin so the set temp compensation the current set temp 24 C For example if the set temp is 24 C the temp compensation is 0 C if the set temp is 25 C the temp compensation is 1 C if the set temp is 30 C the temp compensation is 6 ...

Page 22: ...e paint tobacco absorbed by indoor unit During operation white fog comes out of indoor unit When in COOL or DRY mode a thin water fog can be seen blown out of unit this is the condensed fog because the suddenly cooled indoor air is blown out Automatically switch into FAN mode during cooling To prevent frost from being accumulated on the indoor unit heat exchanger it sometimes auto matically switch...

Page 23: ...after unit autom atically stops Water or vapor generated from the outdoor unit during heating This happens when the frost accumulated on the outdoor unit is removed during defrosting operation Defrosting operation Please check the following things about your air conditioner before making a service call Unit fails to start Is the power supply switch on Power supply switch is not in ON position Is c...

Page 24: ...n or at wrong position or short circuit Faulty temperature sensor Tc2 3 TIMES Sensor disconnected or broken or at wrong position or short circuit Faulty temperature sensor Tm 4 TIMES Sensor disconnected or broken or at wrong position or short circuit Faulty EEPROM on indoor unit PCB 5 TIMES Faulty indoor unit PCB Abnormal communication between indoor and outdoor unit Wrong connection or the wires ...

Page 25: ...HAIER GROUP Qingdao Haier Air Conditioner Electric Co Ltd Address Haier Garden Qianwangang Road Economic Development Zone Qingdao Shandong 266555 P R China Web Site http www haier com ...

Reviews: