•  If the air conditioner is transferred to a new user, this manual shall be transferred to the user, together with the 

conditioner.

•  Before installation, be sure to read Safety Considerations in this manual for proper installation.

•  The safety considerations stated below is divided into " WARNING" and "

 CAUTION

". The matters on severe 

accidents caused from wrong installation, which is likely to lead to death or serious injury, are listed in " WARNING". 

However, the matters listed in "

 CAUTION

" are also likely cause the severe accidents. In general, both of them are 

the important items related to the security, which should be strictly abided by.

•  After the installation, perform test run to make sure everything is in normal conditions, and then operate and maintain 

the air conditioner in accordance with the User Manual. The User Manual should be delivered to the user for proper 

keeping.

  

WARNING

•  Please ask the special maintenance station for installation and repair. Water leakage, electric shocks or fire accidents 

might be caused from improper installation if you conduct the installation by your own.

• 

T

he installation should be conducted properly according to this manual. Water leakage, electric shocks or fire accidents 

might be caused from improper installation.

•  Please make sure to install the air conditioner on the place where can bear the weight of the air conditioner. The air 

conditioner can't be installed on the grids such as the non-special metal burglar-proof net. The place with insufficient 

support strength might cause the dropdown of the machine, which may lead to personal injuries. 

• 

T

he installation should be ensured against typhoons and earthquakes, etc. The installation unconformable to the 

requirements will lead to accidents due to the turnover of the machine.

• 

S

pecific cables should be used for reliable connections of the wirings. Please fix the terminal connections reliably to 

avoid the outside force applied on the cables from being impressed on the cables. Improper connections and fixings 

might lead to such accidents as heating or fire accidents.

• 

C

orrect shapes of wirings should be kept while the embossed shape is not allowed. The wirings should be reliably 

connected to avoid the cover and the plate of the electrical cabinet lipping the wiring. Improper installation might cause 

such accidents as heating or fire accidents.

•  While placing or reinstalling the air conditioner, except the specific refrigerant (R410A), don't let the air go into the 

refrigeration cycle system. The air in the refrigeration cycle system might lead to the cracking or personal injuries due to 

abnormal high pressure of the refrigeration cycle system.

• 

D

uring installation, please use the accompanied spare parts or specific parts. If not, water leakage, electric shocks, fire 

accidents or refrigerant leakage might be caused.

• 

D

on't drain the water from the drainpipe to the waterspout where may exist harmful gases such as sulfureted gas to 

avoid the harmful gases entering into the room.

• 

D

uring installation, if refrigerant leakage occurs, ventilation measures should be taken, for the refrigerant gas might 

generate harmful gases upon contacting the flame.

• 

A

fter installation, check if any refrigerant leakage exists. If the refrigerant gas leaks in the room, such things as air 

blowing heaters and stoves, etc. may generate harmful gases.

• 

D

on't install the air conditioner at the places where the flammable gases may leak. In case the gas leakage occurs 

around the machine, such accidents as fire disasters may be caused.

• 

T

he drainpipe should be properly mounted according to this manual as to ensure the smooth drainage. In addition, heat 

preservation should be taken to avoid condensation. Improper drainpipe mounting might cause water leakage, which 

will get the articles at home wet.

• 

T

he refrigerant gas pipe and liquid pipe should be heat insulated to preserve heat. For inappropriate heat insulation, the 

water caused from the condensation will drop to get the article at home wet.

Safety

• 

T

he air conditioner should be effectively grounded. Electric shocks may occur if the air conditioner is ungrounded or 

inappropriately grounded. The wire for earthing shouldn't be connected to the connections on the gas pipe, water pipe, 

lightning rod or telephone.

• 

T

he breaker for electricity leakage should be mounted. If not, accidents such as electric shocks may happen.

• 

T

he installed air conditioner should be checked for electricity leakage by being powered.

• 

I

f the ambient humidity bigger than 80%, when the water discharge hole be blocked or the filter becomes dirty, or airflow 

speed change, there maybe leads to condensing water drop down, and at the same time there maybe  some drops of 

water spit out.

   CAUTION

Summary of Contents for AC092MDERA

Page 1: ...Manual AC092MDERA AC122MDERA AC162MDERA AC182MDERA AC242MDERA AC282MDERA AC302MDERA AC382MDERA AC482MDERA No 0150538640 Please read this manual carefully before using Keep this operation manual for future reference Original instructions ...

Page 2: ...er 12 hours Operating Range of Air Conditioner Cooling dry Indoor Max DB 32 C WB 23 C Min DB 18 C WB 14 C Outdoor Max DB 43 C WB 26 C Min DB 5 C Heating Indoor Max DB 27 C Min DB 15 C Outdoor Max DB 21 C WB 15 C Min DB 15 C User Manual Warning If the supply cord is damaged it must be replaced by the manufacturer its service agent or similarly qualified persons in order to avoid a hazard This appli...

Page 3: ...2 1 Air Guide Plate Positioning Swing Range All Covered Decide upon a proper angle when guide plates move in auto airflow mode and press Wind Direction button to fix wind direction Upper lower flaps commanding airflow directions shall be positioned as follow when fixing wind directions Upward in cooling and drying mode Downward in heating mode Make sure that outlet plates or flaps are adjusted onl...

Page 4: ...net lipping the wiring Improper installation might cause such accidents as heating or fire accidents While placing or reinstalling the air conditioner except the specific refrigerant R410A don t let the air go into the refrigeration cycle system The air in the refrigeration cycle system might lead to the cracking or personal injuries due to abnormal high pressure of the refrigeration cycle system ...

Page 5: ...ything in the grid in case danger may occur Avoid cold wind from blowing out During heating running the fan of indoor units will not rotate immediately as to prevent cold wind from blowing out Changing Wind Speeds In the state of refrigerating with automatic blowing mode the wind speed automatically decreases when the room temperature approaches the setting In the state of heating when the room te...

Page 6: ...ng period of storage 3 minute protection To protect the unit compressor can be actuated with at least 3 minute delay after stopping Close the window to avoid outdoor air getting in Curtains or window shutters can be put down to avoid the sunshine Do not touch the switch with the wet hand to avoid power shock Stop running and switch off the manual power switch when cleaning the unit During the oper...

Page 7: ...move it Clean up air screens according to their different types For more information please make contact with after service staff Wipe dust with water or dust collector A Wipe dust with dust collector Cleaning Wind Deflector Do not wipe the wind deflector with water forcibly to avoid falling off Before Operating Season 1 Please make the following checkup If abnormal condition occurs consult the af...

Page 8: ... sounds of refrigerant flowing Otherwise when other indoor units performs heating operation white steam may occur during refrigerating operation cold air may appear Clicking sound when switching the air condition on When the conditioner is powered on the sound is made due to the resetting of the expansion valve Please make another check Start or stop working automatically Check if it is in the sta...

Page 9: ...loor surface shall not exceed 2 7m 2 Make sure that outlet airflow covers the whole room area and arrange connecting tubes wires and drain pipes to proper outdoor positions 3 Make sure that ceiling structures are capable of bearing unit weight 4 Connecting tubes drain pipes and connecting wires can be put across walls to connect indoor unit and outdoor unit 5 Connecting tubes and drain pipes betwe...

Page 10: ...head Refer to Figure 3 Figure 2 Figure 3 Remove the Side cover 1 Remove the screw 2 Push the Side cover according to the direction of the rrowhead 3 Then remove the Side cover Side cover screw Cut intake grill for drain pipe 1 Tools Knife or Pliers 2 Cut the intake grill before installing the drain pipe Then pass the drain pipe through the hole As the following schematic Location of the cut After ...

Page 11: ...t to household usables or obstacles as shown with figure Left Right Over 30cm Over 30cm 4 Ceiling Installation Left Right a b Ceiling c Model a b c AC092 182MDERA Over 30cm Over 30cm Over 2cm AC242 482MDERA Over 80cm Over 150cm Over 10cm Ceiling Installation 1 Use Ø10 hanger bolts prepared on the site Please refer to figure on the right when installing When the unit is installed in the ceiling sid...

Page 12: ...02MDERA 1204 AC382MDERA AC482MDERA 1530 3 Installing Hanger Bolt Use M10 hanger bolt prepared on the site featuring 60mm hole depth clearance fixed according to size proposed in the air conditioner external view install according to different building structure specifications to guard against safety faults and leveling instruments shall be available to ensure balanced installation 4 Please use hex...

Page 13: ...ht hexagon bolt to fix air conditioner Leveling is forbidden after air conditioner is installed please make adjustment according to diagram indication According to requirements on the site drain pipes shall be prepared by users on their own resources and make sure that these are connected to drain pipes previously available with the unit make sure that measures are taken to guard against water lea...

Page 14: ... gradient of over 1 100 S shape elbow max height about 10cm down gradient of over 1 100 VP30 Piping Materials Heat Insulating Materials As to prevent condensation heat insulating treatment should be performed The heat insulating treatment for piping should be done respectively Confirming water drainage During the test run check the condition of water drainage and make sure that there is no leakage...

Page 15: ... Enlarging Connecting Cutting or enlarging pipes should be proceeded by installation personnel according to the operating criterion if the tube is too long or flare opening is broken 1 Connecting circular terminals The connecting method of circular terminal is shown in the Fig Take off the screw connect it to the terminal tier after heading it through the ring at the end of the lead and then tight...

Page 16: ...e elbow and fastened with the pressing clip Controller wiring and refrigerant tubing can be arranged and fixed together The machine can t be powered on before electrical operation Maintenance should be done while the power is shut down Seal the thread hole with heat insulating materials to avoid condensation Signal line and power line are separately independent which can t share one line Note the ...

Page 17: ...le SW01 on other sub units of line control are set to 1 2 3 and so on in turn Please refer to the code setting B One line control controls one indoor unit as shown in the above figure indoor unit 6 19 The indoor unit and the line control are connected via three lines with polarity C Two line controls control one indoor unit as shown in the figure indoor unit 20 Either of the line controls can be s...

Page 18: ...aker A Rated current of residual Circuit Breaker A Ground Fault Interruptor mA Response time S Cross Sectional Area of Signal Line Outdoor indoor mm2 Indoor indoor mm2 7 2 5 20 10 10 A 30 mA 0 1S or below 2 cores 0 75 2 0 mm2 shielded line 7 and 11 4 20 16 16 A 30 mA 0 1S or below 11and 16 6 25 20 20 A 30 mA 0 1S or below 16 and 22 8 30 32 32 A 30 mA 0 1S or below 22 and 27 10 40 32 32 A 30 mA 0 1...

Page 19: ...for address setting Set SW03_1 0N and SW03_ 2 OFF SW03_3 SW03_ 4 SW03_5 SW03_6 SW03_7 and SW03_ 8 are address codes which are set according to actual address Address setting function of wired controller for ultrathin card machine is disnabled SW03_1 Manner of set address 0 Set the address with wired controller or automatism default 1 Set the address with dip switch SW03_2 SW03_8 Set the Communicat...

Page 20: ...Lamp RemoteController Fault Descriptions 1 1 Fault of indoor unit ambient temp transducer TA 2 2 Fault of indoor unit pipe temp transducer TC1 3 3 Fault of indoor unit pipe temp transducer TC2 5 5 Fault of indoor unit EEPROM 6 6 Fault of communication between indoor outdoor units 7 7 Fault of communication between indoor unit and wired control 8 8 Fault of indoor unit water drainage 9 9 Fault of d...

Page 21: ...conditioning the content of lead mercury hexavalent chromium polybrominated biphenyls and polybrominated diphenyl ethers are not more than 0 1 mass fraction and cadmium is not more than 0 01 mass fraction Please recycle the refrigerant before scrapping moving setting and repairing the air conditioning for the air conditioning scrapping should be dealt with by the qualified enterprises ...

Page 22: ......

Page 23: ......

Page 24: ...Qingdao Haier Air Conditioner Electric Co Ltd Haier Industrial Park Qianwangang Road Eco Tech Development Zone Qingdao 266555 Shandong P R C ...

Reviews: