16

Drainage Test

Conduct a drainage test after completion of the electrical work.
During the trial, make sure that drain flows properly through the piping and that no water leaks
from connections.
In case of a new building, conduct the test before it is furnished with the ceiling.
Be sure to conduct this test even when the unit is installed in the heating season.

Procedures

Supply about 1000 cc of water to the unit through the air outlet using a feed water pump.
Check the drain while cooling operation.

(g)

1

2

3

4

1

2

VP 30

Secure the elevation as high as possible
(approx. 100 mm)

A downhill grade of
1/100 or more

When constructing drain piping for several units,
position the common pipe about 100 mm below
the drain outlet of each unit as shown in the sketch.
Use VP-30(11/4") or thicker pipe for this purpose.

(d)

(e) The stiff PVC pipe put indoor side should be heat insulated.

(f) Avoid putting the outlet of drain hose in the places with irritant gas generated. Do not insert the drain

hose directly into drainage, where the gas with sulfur may be generated.
Backwater bend

Because the drain spout is at the position, which negative pressure may occur. So with the rise of water
level in the drain pan, water leakage may occur. In order to prevent water leakage, we designed a
backwater bend.
The structure of backwater bend should be able to be cleaned. As the below figure shown, use T type joint.
The backwater bend is set near the air conditioner.

As figure shown, set a backwater bend in the middle of drain hose.

H

1

H

2

H1=100mm or the static pressure of air sending motor

H2=1/2H1 (or between 50~100mm)

6.  Installation of air suction and discharging duct

A

Insulation

muffler cavity (air sending)

Sacking joint

Air volume adjuster

Air outlet

Enlarging chart of
profile chart A

Vibration resistance hook

Checking meatus

Air conditioner

main unit

Ceiling

Air suction grille with air filter

Please consult the after-sales service worker of Haier Air Conditioner for the choosing and installation
of suction inlet, suction duct, discharging outlet and discharging duct. Calculating the design drawing
and outer static pressure, and choose the discharging duct with proper length and shape.

Installation Manual For Indoor Unit

Summary of Contents for AD282AHEAA

Page 1: ...A DUCT TYPE AIR CONDITIONER AD282AHEAA AD362AHEAA AD482AHEAA AD602AHEAA Operation Instruction Manual Please read this operation manual before using the air conditioner Please keep this manual careful...

Page 2: ...intenance 9 For Preparation of Heating Hot Keep 10 Is The Unit Installed Correctly 11 Installation Manual For Indoor Unit 12 20 Installation Manual For Electric Wiring 21 Safety Precautions 3 5 Parts...

Page 3: ...an appropriate anti pollution method of disposal Disposal of the packaging of your new air conditioner All the packaging materials employed in the package of your new air conditioner may be disposed w...

Page 4: ...ident by some improper handing Do not install nearby the place where may have leakage of flammable gas Depending on the place of installation a circuit breaker may be necessary Drain pipe should be ar...

Page 5: ...of such equip ment which generates steam condensed water may drip during cooling operation or it could cause a fault current or short circuit When operating the system simultaneously with a combustio...

Page 6: ...e During installa tion when the connecting cables break off it must be assured that the grouding wire is the last one to be broken off 6 The breaker of the air conditioner should be all pole switch an...

Page 7: ...6 Indoor Unit Air outlet Air inlet Duct Duct Drainpipe Parts and Functions...

Page 8: ...cle exist at the air inlet or outlet Cooling is not sufficient Isn t sun shine invading direct Isn t any unexpected heating load generated Isn t the room much crowded Isn t the swing louver horizontal...

Page 9: ...e FAN mode during cooling To prevent frost from being accumulated on the indoor unit heat exchanger it is sometimes automatically switched to the FAN mode but it will soon return to the cooling mode E...

Page 10: ...the air inlet and air outlet of both indoor and outdoor units Make sure that the air filter is not dirty Cut in the power supply switch 12 hours before starting run Post Season Care Operate the unit...

Page 11: ...RMING OPERATION Heat pump type warming Defrosting operation Atmospheric temperature and warming capacity Period of warm up With the heat pump type warming the mechanism of heat pump that concentrate h...

Page 12: ...The place where salt breeze blows Seaside etc The place where dense soot smoke exists The place where humidity is extraordina rily high The place where near the machine which radiates the electromagn...

Page 13: ...can result from a falling of the unit Execute the prescribed installation construction to prepare for earthquakes and the strong winds of typhoons and hurricanes etc Improper installations can result...

Page 14: ...he chosen installation place should meet the following requirements and get the user s consent Place ensures ideal airflow distribution The passage of airflow has no obstacles When importing outside a...

Page 15: ...ion wire indoor and outdoor unit connection wire of indoor unit so that after installation they can be immediately connected with outdoor unit Cut the opening on the ceiling Maybe it needs to strength...

Page 16: ...ain unit VP 25 joint field purchased Pipe cover large for insulation accessory VP 25 field purchased Pipe cover for insulation field purchased Drain hose accessory Pipe cover small for insulation acce...

Page 17: ...nage where the gas with sulfur may be generated Backwater bend Because the drain spout is at the position which negative pressure may occur So with the rise of water level in the drain pan water leaka...

Page 18: ...adrate air duct Presuming the unit length friction impedance of the duct is 1Pa m when the dimension of one side of the air duct is fixed as 250mm as shown below Note 1Pa m 0 1mmAg m The chosen chart...

Page 19: ...d The result is because of the irregular outer air mass strong wind and sunshine the humidity is increased There may be water drop on the outside of duct For cement and other new constructions even if...

Page 20: ...ory the capacity number of fan controller is set at No 5 Rotate this switch capacity number setting No 1 No 8 Once the fan controller has trouble this linker can perform emergency assistant control Wh...

Page 21: ...pipe leaks then do heat insulation treatment as below figure shown Only use seal cushion to bind the joint part of air pipe and heat insulation parts Paste the refrigerant oil here Torque spanner Span...

Page 22: ...low This table shows 20 m length wires with less than 2 voltage drop 2 Wiring connection Make wiring to supply power to the outdoor unit so that the power for the indoor unit is supplied by terminals...

Page 23: ...for more than 2m continuously CT check abnormal 3 times in 30m Fault phase short of phase out of balance greatly High pressure switch acts 3 times in 30m Low pressure switch acts in normal running Co...

Page 24: ...HAIER GROUP Qingdao Haier Air Conditioner Electric Co Ltd Address Haier Garden Qianwangang Road Economic Development Zone Qingdao Shandong 266555 P R China Web Site http www haier com...

Reviews: