Service diagnosis
Disconnect the compressor harness connector from the outdoor unit PCB.
To disengage the connector, press the protrusion on the connector.
Then, measure resistance between P (+) and N (-) and the U, V and W terminals of the compressor
connector with a multi-tester. Evaluate the measurement results for a pass/fail judgment.
N(-)terminal of tester(P(+)for digital tester)
P(+)
UVW
P(-)
UVW
P(+)terminal of tester(N(-)for digital tester)
UVW
P(+)
UVW
P(-)
Normal resistance
Unacceptable resistance
Short (0
or open
Domestic air conditioner
Turn off the power. check if the
compressor wiring connected ok or not
Reconnect the wiring
NO
YES
Check the IPM module
NO
Change the IPM
YES
Test the resistance values among
phases U, V and W of compressor, is
the resistance is about 1
?
YES
Check the installation condition
Replace the
compressor
42
Summary of Contents for AS12GB3HRA
Page 12: ... Piping diagrams Domestic air conditioner 5ˊPinping diagrams 10 ...
Page 58: ... Circuit diagrams Domestic air conditioner ...
Page 60: ...Removal of procedure 1 Removal of Air Filter 1 Domestic Air Condition ...
Page 63: ...Removal of procedure three two HOOKS 4 Domestic Air Condition ...
Page 65: ...Removal of procedure 4 Removal of Drain pan 6 Domestic Air Condition ...
Page 66: ...Removal of procedure 5 Removal of vertical blades and swing motor 7 Domestic Air Condition ...
Page 67: ...Removal of procedure 6 Removal of Electrical Box 8 Domestic Air Condition ...
Page 68: ...Removal of procedure 7 Removal of Heat Exchanger 9 Domestic Air Condition ...
Page 69: ...Removal of procedure 10 Domestic Air Condition ...
Page 70: ...Removal of procedure 8 Removal of Fan Rotor and Motor 11 Domestic Air Condition ...
Page 71: ...Removal of procedure 12 Domestic Air Condition ...