Service Diagnosis
42
YES
Check the indoor PCB: only indoor
charged measure the voltage
between 3 and 4 of IC6 on the indoor
PCB with a universal meter. And
measure the voltage between
CN23(S) and CN17 (L) with a
universal meter.
If the voltage is a constant
value from DC 0V to DC 5V.Or
the voltage between
communication line (red) and N
(white line) is not close to18V
DC when only indoor charged.
The indoor PCB is
damaged; replace it
with a new one.
Test the outdoor power is
supply 230VAC with a
universal meter when indoor
and outdoor are charged.
Check the cable
between outdoor
and power
NO
YES
NO
YES
LED2 light of the outdoor
The module PCB is
damaged. Replace
it with a new one.
NO
YES
LED 1 light
YES
Measure the voltage
between 3 and 4 of IC9 on
the Outdoor mainboard
with a universal meter .The
voltage is a constant value
of 0V DC to 5V DC
The outdoor PCB is
damaged. Replace
it with a new one.
NO
Outdoor PCB is ok then check
cable.
Summary of Contents for AS35RBAHRA-PL
Page 12: ...Piping diagrams Domestic air conditioner 5 Piping diagrams 10 9 52CuT 9 52CuT 6 35CuT 6 35CuT...
Page 15: ...Printed circuit board connector wiring diagram 13 Domestic air conditioner Wiring diagrams...
Page 50: ...Circuit diagrams 49 Domestic air conditioner 11 Circuit Diagrams...
Page 51: ...Circuit diagrams 50 Domestic air conditioner...
Page 55: ...three 6 Removal Procedure 54 Domestic Air Conditioner Remove the casing 1 2 3...
Page 59: ...Removal Procedure 58 Domestic Air Conditioner motor cover motor cover...
Page 60: ...Removal Procedure 59 Domestic Air Conditioner...