runs without
stop,
temperature
in freezer is
too low
been set to “over cooling” position.
2.The contacting point of temperature
controller is adhered.
3.The temperature sensing probe of
controller is not placed well, and causes
maladjustment
4.Compressor efficiency reduced.
moderate.
2. Repair or change.
3. Adjust to suitable position,
normally contact tightly with
evaporator cover.
4.Change compressor.
Compressor
buzzes and
cannot be
started,
thermal
protection
unit jump
repeatedly.
1. Voltage is too low.
2. Starting relay out of order.
3. The starting coil of starting motor is
broken.
4. Compressor does not run.
1.
Supplement a stabilizer,
adjust to rated value.
2. Change starting relay.
3. Change
compressor.
4.The shaft and piston in the
compressor is blocked, please
change.
After short
time of
operation,
over load
protection
unit cuts off
1. The voltage is too high.
2. Over load protection unit is not good, it
jumps earlier.
3. Starter contacting point is adhered.
4. There is short circuit in compressor.
5. There is mechanical problem in the
compressor.
6. Temperature around compressor is too
high.
1. Supplement a stabilizer and
adjust its value to rated.
2. Change over load protection
unit.
3. Change starting relay.
4. Change
compressor.
5. Change
compressor.
6.Increase heat radiation space.
Too much
noise when
compressor
runs
1. The floor is loose.
2. The freezer body is not stable and in
level.
3. When compressor runs, friction
between tubes and freezer body causes
resonance.
4. Compressor fixing screw is loose.
5. The vibration absorption cushion for
compressor fixing is too tight, or too
loose or ageing.
6. Compressor inside noise is too big or
vibration absorption suspending spring
is broken.
1. Reinforce the floor.
2. Make the freezer body stable.
3. Move the tube a little away to
avoid friction.
4. Make the screw tight.
5. Adjust the degree of tight or
loose of vibration absorption
cushion, or change cushion.
6. Change
compressor.
There is no
frost at
evaporator
1. There is serious leakage of
refrigerant.
2. There is dirt blocked the capillary or
system.
1.
Check leakage, make
welding repair, and fill
refrigerant again.
2. Clean the capillary or change
filter.
Frost at
evaporator is
1. There is some leakage of refrigerant.
2. There is dirt block, but not serious.
1. Check leakage, make welding
repair, and fill refrigerant again.