28
rotating
locked.
33
E47
(
-01/02
)
Compressor reverse phase detection protection
One lock
34
E48
(
-01/02
)
Fault in overcurrent protection of system fan
One lock
35
E49
(
-01/02
)
High-pressure protection of system
3 times in 60min,
locked.
36
E51
(
-01/02
)
Over-current protection of system compressor
3 times in 60min,
locked.
37
E52
(
-01/02
)
Open circuit or short circuit in exhaust temperature
sensor of system compressor
recoverable
38
E53
(
-01/02
)
Open circuit or short circuit in coil (outlet) temperature
sensor 1 of system
recoverable
39
E54
(
-01/02
)
Open circuit in low-pressure sensor of system
recoverable
40
E55
(
-01/02
)
Low pressure protection of system
3 times in 60min,
locked.
41
E56
(
-01/02
)
Open circuit or short circuit in suction temperature
sensor of system
recoverable
42
E58
(
-01/02
)
Over temperature of exhaust temperature sensor of
system compressor
3 times in 60min,
locked.
43
E59
(
-01/02
)
Over temperature of coil (outlet) temperature sensor
1/2 of system
recoverable
44
E60
(
-01/02
)
Open circuit or short circuit in coil (outlet) temperature
sensor 1 of system
recoverable
45
E64
Overload protection of system pump in air conditioning
side
One lock
46
E65
Overload protection of system eletrical assisted heater
in air conditioning side
One lock
47
E68
Overtop or low protection of outdoor ambient
temperature
recoverable
48
E69
(
-01/02
)
Refrigerant lack protection of system
One lock
49
E71
Overtop Temperature difference of in and out water
3 times in 60min,
locked.
50
E72
Running time exceeded
One lock
51
E76
(
-01/02
)
Lower temperature of exhaust temperature sensor of
system compressor
3 times in 60min,
locked.
52
E77
(
-01/02
)
Open circuit or short circuit in oil temperature sensor of
system
recoverable
53
E78
(
-01/02
)
Lower temperature of oil temperature sensor of system
3 times in 60min,
locked.
54
E79
(
-01/02
)
Over temperature of oil temperature sensor of system
3 times in 60min,
locked.
55
E80
(
-01/02
)
Open circuit in high-pressure sensor of system
recoverable
56
E81
(
-01/02
)
High pressure system protection
3 times in 60min,
locked.
57
E82
(
-01/02
)
Fault in system four-way valve switching
3 times in 60min,
locked.
58
E83
(
-01/02
)
The system
compression ratio ε is too high for
protection
3 times in 60min,
locked.
59
E84
(
-01/02
)
The system compression ratio ε is too low for protection
3 times in 60min,
locked.
60
E85
(
-01/02
)
System oil temperature preheating
recoverable
61
E218
EE fault of mainboard
One lock
Note:
1
、
The 60 minutes time of the accumulated three times within 60 minutes is calculated with natural time;
2
、
The flicker of the fault lamp is related to its corresponding number except that E72 does not flicker.
3
、
After 4 minutes of communication between the wired controller and the unit, it still displays "in
communication, please wait a moment..." The reason may be for multiple units to dial the code set to the
host.