28
During the use of the unit, certain routine inspections must be carried out to ensure the performance of the unit.
This is also to avoid unnecessary downtime routine inspections including the following items:
Item details
Per month
Each quarter
Half a year
One year
Base on needs
1.Compressor
Performance evaluation, with
or without abnormal sound
●
Is the wiring secure
●
Whether the current is abnormal
(within 10%)
★
Compressor exhaust temperature
★
Detecting oil level
★
Check the color of the lubricant
★
2. Controller
Check parameter settings
★
Inspection protection
★
Delay protector
★
Phase sequence protector
★
High and low voltage switch
★
Water pressure difference switch,
water flow switch
★
Overload protector
★
Exhaust gas temperature protector
★
3.Shell and tube heat exchanger
Check water quality
●
Cleaning shell-and-tube heat
exchanger
★
Seasonal protection measures
(winter antifreeze)
★
4.Finned heat exchanger
Cleaning fins
★
5.Other
Does the Y filter need to be
replaced and cleaned?
●
Is the unit screw loose?
●
6.7 Maintenance
Remarks: The above maintenance plan is only for guidance (for reference), and the specific 26 maintenance plan
can be carried out according to different usage conditions in different regions. Description:
●
for user self-test
items;
★
check items for professionals.