HAIER CHILLER
2
6
7
3#compressor overload protection
Er: 03
3#compressor stops
Serious fault
8
1#system high pressure protection
Er: 04
System 1 stops
Serious fault
9
2#system high pressure protection
Er: 05
System 2 stops
Serious fault
10
3#system high pressure protection
Er: 06
System 3 stops
Serious fault
11
Secondary module flow protection
Er: 07
Secondary module stops
Serious fault
12
1#system low pressure protection
Er: 11
System 1 stops
Serious fault
13
2#system low pressure protection
Er: 12
System 2 stops
Serious fault
14
3#system low pressure protection
Er: 13
System 3 stops
Serious fault
15 Open/short circuit of temperature–sensing
circuit of liquid pipe 1
Er: 14
System 1 stops
Serious fault
16 Open/short circuit of temperature–sensing
circuit of liquid pipe 2
Er: 15
System 2 stops
Serious fault
17 Open/short circuit of temperature–sensing
circuit of liquid pipe 3
Er: 16
System 3 stops
Serious fault
18
Outdoor fan overload protection
Er: 17
Unit stops
Serious fault
19
Secondary module phase sequence protection
Er: 18
Secondary module stops
Serious fault
20 Open/short circuit of temperature–sensing
circuit of coil pipe 1
Pr: 01
Defrosting
without
inspection
Restorable
21 Open/short circuit of temperature–sensing
circuit of coil pipe 2
Pr: 02
Defrosting
without
inspection
Restorable
22 Open/short circuit of temperature–sensing
circuit of coil pipe 3
Pr: 03
Defrosting
without
inspection
Restorable
23
Cooling and frost-proof protection of 1 # system
Pr: 04
Protective operating (no
maintenance needed)
Restorable
24
Cooling and frost-proof protection of 2 # system
Pr: 05
Protective operating (no
maintenance needed)
Restorable
25
Cooling and frost-proof protection of 3 # system
Pr: 06
Protective operating (no
maintenance needed)
Restorable
26 Open/short circuit of external circuit
temperature-sensing circuit
Po; 01
Defrosting
without
inspection
Restorable
27
Frost-proof protection in winter
Po;
06
Protective operating (no
maintenance needed)
Restorable
12.6.2 When a fault is present, controller gives an alarm and fault module number glistens. Pressing the
query key now can show the fault code and the fault can be resolved automatically.
12.6.3 After the fault is resolved, the indication of a serious fault will still display, only after pressing the
“reset/dark” key will the system return to operating condition before the fault occurred. As for restorable
faults, such as temperature sensor fault, when the fault is resolved, the unit restores automatically.
12.7 Main technical parameter
12.7.1 Running voltage
Transformer of controller: primary side 220V/AC second side
①
16V/AC
Frequency 50HZ second side
②
11.5V/AC