58
/
88
PICTURE
6
5. Infusion flow of freezing medium
①
The
schematic
diagram
of
each
freezing
medium
cylinder
②
Infusion
flow
of
freezing
medium
When
infusing
high
temperature
level
freezing
medium,
machine
shall
be
under
the
status
of
stop,
firstly,
infuse
R134Afreezing
medium,
then
infuse
R404Afreezing
medium;
to
ensure
that
freezing
medium
can
be
infused
successfully
at
one
time,
at
the
time
of
infusing
above
freezing
mediums,
cylinders
must
be
placed
upside
down
to
infuse
liquid.
As
the
infusion
quantity
of
low
temperature
level
freezing
medium
is
small,
and
the
requirement
for
the
infusion
quantity
of
freezing
medium
is
very
strict,
if
infusion
quantity
is
not
accurate,
refrigerating
effect
will
be
directly
affected.
As
low
temperature
freezing
medium
has
high
pressure,
freezing
medium
in
cylinder
is
small,
so
you
are
required
to
prepare
everything
in
advance
when
you
are
going
to
infuse
low
temperature
level
freezing
Summary of Contents for DW-86L338
Page 7: ...7 88 Product appearance DW 86L388 486 628 728 828...
Page 8: ...8 88 DW 86L288 DW 86L338 388A...
Page 9: ...9 88 DW 86L490 DW 86W100...
Page 10: ...10 88 DW 86W420...
Page 11: ...11 88 Dimensions DW 86W100...
Page 12: ...12 88 DW 86L490...
Page 29: ...29 88 product nameplate For example DW 86L338...
Page 55: ...55 88 PICTURE 2 PICTURE 3 PICTURE 4 U Unit Pa 3Pa...