6.2.3 Low pressure protection
The low pressure is controlled by simulating evaporating temperature:
When cooling, compare the evaporating temp. with the compressor suction temp. and choose the lower one (Teva c)
to compare.
-25°C
Teva_c
-30°C
-35°C
-40°C
-45°C
If it lasts 5 seconds, unit will stop and Alarm.
After standing by 3 minutes, unit will restart. If
it happens 3 times in 60 minutes, unit will stop
and alarm for ever. It will disappear if unit back to
power.
The lowest running frequency 20HZ
The lowest running frequency 20HZ
The lowest running frequency 20HZ
Normal running
In the heating mode, low pressure protection is realized by the lower temperature (Teva h) from a comparison of the
defrost temperature (Te) and ambient (Tc) temperature.
Teva_h
-30°C
-35°C
-40°C
-45°C
-50°C
If it lasts 5 seconds, unit will stop and Alarm.
After standing by 3 minutes, unit will restart. If it
happens 3 times in 60 minutes, unit will stop and
lock out. It will disappear when the unit has power
restored.
The lowest running frequency 20HZ
The lowest running frequency 20HZ
The lowest running frequency 20HZ
Normal running
Summary of Contents for FlexFit Pro AL24LP2VHA
Page 1: ...SYJS 04 2017REV B Edition 2017 04 FlexFit PRO ...
Page 8: ...FlexFit Pro 6 ...
Page 9: ......
Page 10: ...AW24LP2VHA AW36LP2VHA ...
Page 11: ......
Page 12: ...10 ...
Page 13: ...11 ...
Page 14: ...12 ...
Page 15: ...13 ...
Page 16: ...14 ...
Page 17: ...15 ...
Page 18: ...16 ...
Page 19: ...17 ...
Page 20: ...18 ...
Page 37: ...35 FlexFit Pro ...
Page 72: ...68 FlexFit Pro 3 Outdoor PCB PCB 0151800054B Power module 0150401824 ...
Page 90: ...86 FlexFit Pro Fig 4 1 ...
Page 91: ...87 FlexFit Pro Fig 4 2 ...