There are three methods to connection wire controller and
the indoor units:
A: One wired controller can control max.up to 16 sets of
indoor units, for Flexifit Pro series indoor units, there are two
connection method
:
Type 1
:
for model AL24/36/42/48LP2VHA,AM24LP2VHA,the
wiring connection between wired controller - the master unit
(directly connected to the wired controller), master unit -
slave unit, slave unit-slave unit should be one to one match of
all three lines.
Type 2
:
for model AM36/42/48LP2VHA,The wiring connection
between wired controller-the master unit (directly connected
to the wired controller) should be three polar wire, and the
wiring between master unit - slave unit, slave unit-slave unit
should be one to one match of two polar lines.
Note: PCB DIP switches are used for setting slave units, please refer
to indoor unit wiring diagram.
B. One wire controller controls one indoor unit, and the indoor
unit connects with the wire controller through 3 pieces of
polar wire.
C. Two wired controllers control one indoor unit. The wire
controller connected with indoor unit is called master one, the
other is called slave one. Master wire controller and indoor
unit; master and slave wire controllers are all connected
through 3 pieces of polar wire.
Note: There are PCB DIP switches for slave or master units
selection, please refer to the indoor unit wiring diagram to get
details.
About the wire:
The wire controller is equipped with special communication
wiring in the accessories. 3-core terminal (1-white 2-yellow 3-
red) is connected with the terminal A, B, C of wire controller
respectively.
*One side of the shielded sheet of communication wire
must be earthed.
Indoor PCB port.
For location
number ,refer
to indoor unit wiring
diagram.
TYPE 2, FOR AM36/42/48LP2VHA
A TYPE 1, FOR AL24/36/42/48LP2VHA, AM24LP2VHA
B
C
Wire controller
port
Wire controller
port
Wire controller
port
Wire controller
port
Wire controller
port
Wire controller
control wiring of
Wire controller
(master unit)
Indoor 1
Indoor 2
Indoor N
Indoor 15
Indoor16
(master unit)
Indoor 1
Indoor 2
Indoor N
Indoor 15
Indoor16
Wire controller
port
Wire controller
port
Wire controller
port
Wire controller
port
Wire controller
port
Wire controller
control wiring of
Wire controller
Wire controller
Polar wire
Wire controller
port wire
Wire controller
port wire
Wire controller
Wire controller
Indoor 1
Indoor 1
The communication wiring is 189ft (4.8 meter) long; if the
actual length is more than it, please distribute wiring
according to below table:
Summary of Contents for FlexFit Pro AL24LP2VHA
Page 1: ...SYJS 04 2017REV B Edition 2017 04 FlexFit PRO ...
Page 8: ...FlexFit Pro 6 ...
Page 9: ......
Page 10: ...AW24LP2VHA AW36LP2VHA ...
Page 11: ......
Page 12: ...10 ...
Page 13: ...11 ...
Page 14: ...12 ...
Page 15: ...13 ...
Page 16: ...14 ...
Page 17: ...15 ...
Page 18: ...16 ...
Page 19: ...17 ...
Page 20: ...18 ...
Page 37: ...35 FlexFit Pro ...
Page 72: ...68 FlexFit Pro 3 Outdoor PCB PCB 0151800054B Power module 0150401824 ...
Page 90: ...86 FlexFit Pro Fig 4 1 ...
Page 91: ...87 FlexFit Pro Fig 4 2 ...