507332-02G / 31-5000663
Page 31 of 35
Issue 2209
NF80D090S4B Performance (Less Filter)
External
Static
Pressure
in. w.c.
Air Volume / Watts at Various Blower Speeds
High
Medium-High
Medium
Medium-Low
Low
cfm
watts
cfm
watts
cfm
watts
cfm
watts
cfm
watts
0.10
1725
390
1495
270
1390
220
1320
195
1145
140
0.20
1695
405
1470
285
1340
235
1280
210
1105
145
0.30
1660
415
1425
300
1290
240
1225
215
1040
160
0.40
1615
430
1395
310
1250
255
1185
230
1005
170
0.50
1570
450
1360
325
1210
265
1145
240
945
180
0.60
1545
465
1295
340
1165
280
1085
255
865
185
0.70
N/A
N/A
1265
350
1120
295
1040
265
810
200
0.80
N/A
N/A
1215
365
1080
305
1000
275
755
210
NF80D110S5C Performance (Less Filter)
External
Static
Pressure
in. w.c.
Air Volume / Watts at Various Blower Speeds
High
Medium-High
Medium
Medium-Low
Low
cfm
watts
cfm
watts
cfm
watts
cfm
watts
cfm
watts
0.10
2385
630
2100
410
1830
310
1610
240
1505
190
0.20
2325
650
2010
440
1760
330
1570
255
1375
195
0.30
2280
675
1940
460
1705
340
1500
260
1320
210
0.40
2235
690
1895
475
1635
365
1440
285
1265
225
0.50
2165
710
1845
490
1595
380
1380
300
1200
235
0.60
2125
735
1800
510
1545
390
1320
310
1170
250
0.70
2090
740
1755
530
1510
405
1285
325
1100
260
0.80
2035
760
1700
540
1460
425
1255
345
1030
275
Allowable Heating Speeds
Model
Red
Yellow
Blue
Brown
Black
045
Not Allowed
Allowed
Factory Setting
Allowed
Not Allowed
070
Not Allowed
Allowed
Factory Setting
Allowed
Not Allowed
090
Allowed
Allowed
Factory Setting
Allowed
Not Allowed
110
Not Allowed
Allowed
Factory Setting
Allowed
Not Allowed
Table 18.
Allowable Circulation Speeds
Model
Red
Yellow
Blue
Brown
Black
All Models
Factory Setting
Not Allowed
Not Allowed
Not Allowed
Not Allowed
Table 19.